Technical Data
12
221457 / 9475621310
2019-01-18·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Digital Output Module 4
-
Channel Version
for Zone 1
Series 9475/32-04-.2
Explosion Protection
Ex i control input
"Plant STOP"
Connection
terminals
X3 1, 2
(without galvanic
separation,
compatible with 9475/22)
X3 3, 4
(with galvanic
separation,
switchable in parallel)
Type of protection
Ex ia
Ex ia
Max. voltage U
o
5.1 V
–
Max. current I
o
0.44 mA
–
Max. power P
o
0.5 mW
–
Max. connectable
inductance L
o
/
capacity C
o
IIC
L
O
[mH]
100
10
2
1
0.2
0.01
–
C
O
[μF]
2.195 2.595 3.295 3.695 5.495 15.995
IIB / IIIC
L
O
[mH]
100
10
2
1
0.2
0.01
–
C
O
[μF]
9.995 12.995 16.995 19.995 31.995 159.995
Max. voltage U
i
–
30 V
Max. internal
resistance R
i
–
4940 Ω
Max. internal
capacity C
i
5.2 nF
(in the above tables,
C
i
is subtracted from C
o
)
negligible
Max. internal
inductance L
i
negligible
negligible
Содержание is1+ 9475/32-04 2 Series