Installation
12
154099 / 8591601300
S-BA-8591-04-en-04/09/2009
Ex Plug Connector miniClix
8591/1, 8591/4
Before fitting the flange socket, device plug and angled adaptors in flameproof
enclosures:
X
Disconnect all connections and wiring from the power supply and secure them against
unauthorised activation.
X
The threaded holes in the flameproof protective enclosure must meet the minimum
requirements of IEC/EN 60079-1 o.
X
Check that the flange socket, device plug and angled adaptors and the corresponding
holes and screw-in threads are intact and clean.
X
Make sure that threads and threaded holes match.
X
Check that the seal ring is positioned correctly and intact.
7.1 Tested cable types
Presently tested cable types to be used with Ex-d plug connector acc. to IEC/EN 60079-
0:
*with separate sealing insert
)
IP68: submerged in 2 m water for one hour.
Torque applied to locking nut
(pressure fitting): 5 Nm
Test weight = diameter x 20 N
Torque applied to locking nut
(pressure fitting): 5 Nm
Test weight = diameter x 20/4 N
X
Ölflex classic 100
X
Ölflex classic 400
X
Ölflex classic 110
X
H07 BQ-F 3G1.5
X
H07 BQ-F 5G1.5
X
JZ-500
X
Y-JZ
X
RD-Y(ST)Y blue
X
JE-LiYCY
X
NYM
X
NYY
X
Ölflex EB001250 R4G1.5
X
H05VV-F 3 G1.0
X
*Unitronic Bus L2/FIP FC
X
*Unitronic Bus FD PL2/FIP FC
UL/CSA
X
JE-Y(ST)Y
X
H07-RN-F 3G1.0
X
H07-RN-F 3G1.5
X
H07-RN-F 3G2.5
X
H07-RN-F 3G0.75
X
H05-RR-F 3G
X
H05-RR-F 3G1.5
X
H05-RR-F 5G1.5
X
Silflex SiHf
X
Sinec LZ bus cable