Maintenance
26
154099 / 8591601300
S-BA-8591-04-en-04/09/2009
Ex Plug Connector miniClix
8591/1, 8591/4
9.1 Regular Maintenance Work
X
Consult the relevant national regulations (e.g. IEC/EN 60079-17) to determine the type
and extent of inspections.
X
Plan the intervals so that any defects in the equipment which may be anticipated are
promptly detected.
To check as part of the maintenance schedule:
X
Check that cables and lines are clamped properly.
X
Inspect device for visible damage.
X
Compliance with the permitted temperatures in accordance with IEC/EN 60079-0.
X
Make sure the device is used according to its designated use.
9.2 Repair work
X
Repairs that may affect the explosion protection are only to be performed by the
manufacturer.
X
No changes to the apparatus are permitted.
X
Maintenance work and repairs may only be performed using original replacement
parts supplied by the manufacturer.
In case of damage to the plug pins:
X
Replace the apparatus. Disassembly cannot be performed, therefore repair is not
possible.
In case of damage to the flameproof enclosure:
X
The device must be returned to the manufacturer for repair.
9.3 Cleaning
X
Clean with a cloth, brush, vacuum cleaner or similar items.
X
When cleaning with a damp cloth, use water or mild, non-abrasive, non-scratching
cleaning agents.
X
Never use aggressive cleaning agents or solvents.