Installation
22
154099 / 8591601300
S-BA-8591-04-en-04/09/2009
Ex Plug Connector miniClix
8591/1, 8591/4
7.9 Direct connection of metal device plug / flange socket using individual wires
11390E00
X
Screw the flange socket (1) or device plug (1) together with the anti-twist device (2) in
the enclosure (threaded hole: M20; wrench size: SW25).
X
Secure the device plug or flange socket against unintentional turning by screwing in
the locking screw (3).
WARNING
Prevent twisting of the components!
X
Secure components against twisting or loosening by taking appropriate measures
(e.g. anti-twist device, see accessories and spare parts).
WARNING
Danger due to damaged cables!
Z
Careless screwing can damage the cables and their insulation.
X
Exercise care when screwing components together.
)
To ensure explosion protection, insert only device plugs and flange sockets
made of metal in the holes of the flameproof enclosures.
)
Test torques: see data sheet or chapter “Technical data“ in these operating
instructions.