Installation
42
147924 / 8537608300
2014-01-13·BA00·III·en·04
Safety switch
8146/5-V37 8150/5-V37
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Earthing assemblies
Assembly
8195
03680E00
Connection cross-section:
1.5 ... 4 mm
2
Torque: 2 Nm
Assembly
85
07871E00
Protective conductor for cable
cross-section of up to 10 mm
2
Outside:
Loosen the screw (3).
Insert the core under the
clamping bracket (4).
Tighten the screws (3)
(4.5 Nm).
Inside:
Unscrew the screw (1).
Put the cable lug onto the
screw.
Tighten the screw (1)
together with the cable lug
(1.4 Nm).
Assembly
245
07855E00
Protective conductor for cable
cross-section
(
25 mm
2
Insert the earth bolt (1) into
a suitable bore of the
enclosure wall (2) and
fasten it by means of a
hexagon nut (3).
Push the inner PE cable
lug (4) onto the earth
bolt (1).
Fasten the PE cable lug
using a split washer and
hexagon nut (5) (16 Nm).
Push the outer PE cable
lug (6) onto the earth
bolt (1).
Fasten the PE cable lug
using a split washer and
hexagon nut (7) (16 Nm).
1
2
4
3
5
4
1
6
7
3
2
1
a
5
a
7
a