Cable lug connection for 8146/5-V37-.05/06/07-... and 8150/5-V37-.05/06/07-...
12441E00
- Remove the protective foil from the insertion prism (6) and glue the insertion prism in
the main terminal (7).
- Insert the clamping plate (5) into the main terminal (7) and tighten the mounting screw
of the main terminal (1) with 6 - 8 Nm.
- Insert the conductor with ring cable lug (4) and split washer (3) into the screw of the
clamping plate and tighten it by means of the nut (2) (5 Nm).
WARNING
Danger due to conducting metal parts!
If a cable lug connection is used, the conducting metal parts are located outside the
switch.
Only operate the switch with installed protection against accidental contact!
WARNING
Danger due to twisted cable lug connection!
Mechanical load on the cable may cause twisting of the cable lug connection on the
clamping plate. Protection against accidental contact ensures anti-twist protection.
Only operate the switch with installed protection against accidental contact or with a
separate anti-twist protection!
WARNING
Danger due to conducting metal parts in case of single conductor connection or
conductors of small cross-section!
If only one conductor or at least one conductor with a cross-section
(
25 mm
2
/ AWG
4 is used, it is possible to come into contact with conducting metal parts even if the
protection against accidental contact is mounted since the openings of the protection
are not sealed completely.
To obtain the degree of protection IP20, mount a suitable covering in addition to the
protection against accidental contact.
For permissible conductor cross-sections refer to "Technical Data".