Installation
35
Safety switch
8146/5-V37 8150/5-V37
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
- Provide suitable back-up fuses, see chapter 5 "Technical Data".
- Use only isolated cables and conductors whose testing voltage is AC 500V and whose
minimum quality is HO5 in intrinsically safe circuits.
- The diameter of one conductor must not be smaller than 0.1 mm; this applies also to
the individual wires of finely stranded conductors.
- EEx i - electric circuits are connected to blue terminal blocks.
- The consumers must be protected against overload independently of it.
Cable glandsTightening torques
Tightening
torque
Main terminals
25 - 30 Nm
Auxiliary
contacts
0.4 Nm
Pick-off terminal
blocks
1.5 - 1.8 Nm
Wiring to terminal blocks:
WARNING
Danger from energised parts!
Risk of severe injuries.
All connections and wiring must be disconnected from the power supply.
Secure the connections against unauthorised activation.
WARNING
Short-circuit in the main circuit
Contacts may be damaged.
Replace the switch after each short circuit in the main circuit (the element
is hermetically sealed and the state of the switching contacts cannot be
checked).
Type 8161
EMSKE
Size of the
cable gland
Connection
thread [Nm]
Pressure screw
[Nm]
Connection
thread /
pressure screw
[Nm]
M 16 x 1.5
1.8
1.3
4
M 20 x 1.5
2.3
1.5
8
M 25 x 1.5
3.0
2.0
10
M 32 x 1.5
4.5
3.0
20
M 40 x 1.5
10.0
10.0
20
M 50 x 1.5
12.0
12.0
30
M 63 x 1.5
16.0
16.0
40
Multiple holes
M 25 x 1.5
5.0
2.0
M 32 x 1.5
7.0
3.0