Installation
34
147924 / 8537608300
2014-01-13·BA00·III·en·04
Safety switch
8146/5-V37 8150/5-V37
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
8146/5-V37-.08-....
8146/5-V37-.09-....
8146/5-V37-.10-....
8150/5-V37-.08-....
8150/5-V37-.09-....
8150/5-V37-.10-....
Main terminals
(directly on the
switch)
Single conductor
connection:
solid, finely
stranded:
6 ... 10 mm
2
(AWG 10 ... AWG 8)
only with insertion
prism
stranded:
35 ... 150 mm
2
(AWG 2... 300 kcmll)
finely stranded: 50 ... 150 mm
2
(AWG 1/0 ... 300 kcmll)
with cable lug:
max. 150 mm
2
(max. 300
kcmll) The degree of pro
-
tection IP2X is not appli
-
cable!
with clamping plate
and insertion prism
Multiple conductor connection:
stranded:
2 x 25 mm
2
... 2 x 50 mm
2
(2 x AWG 4 ...
2 x AWG 1/0)
*)
finely stranded: 2 x 35 mm
2
... 2 x 50 mm
2
(2 x AWG 2 ...
2 x AWG 1/0)
*)
finely stranded
with core end
sleeve:
2 x 25 mm
2
... 2 x 50 mm
2
(2 x AWG 4 ...
2 x AWG 1/0)
*)
with cable lug:
max. 2 x 150 mm
2
(max. 2 x 300 kcmll)
**)
with clamping plate
and insertion prism
*) Only conductors of the same cross-section are permissible!
**) Conductors with different cross-sections are permissible! For
cross-sections < 70 mm
2
, the degree of protection IP2X is not ap
-
plicable!
Auxiliary
contacts
solid, finely
stranded:
1.5 ... 2.5 mm
2
(AWG 16 ... AWG 14)
Pick-off termi
-
nal blocks
Single conductor
connection
solid, finely
stranded:
0.5 ... 10 mm
2
(AWG 20 ... AWG 8)
Multiple conductor connection (only for conductors with the same
cross-section):
solid, finely
stranded:
max. 2 x 6 mm
2
(max. 2 x AWG 10)
Содержание 8146/5-V37 Series