147924 / 8537608300
2014-01-13·BA00·III·en·04
Installation
33
Safety switch
8146/5-V37 8150/5-V37
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
with cable lug:
max. 2 x 50 mm
2
(max. 2 x AWG 1/0)
**)
with clamping plate
and insertion prism
*) Only conductors of the same cross-section are permissible!
**) Conductors with different cross-sections are permissible! For
cross-sections < 25 mm
2
/ AWG 4, the degree of protection IP20 is
not applicable!
Auxiliary
contacts
solid, finely
stranded:
1.5 ... 2.5 mm
2
(AWG 16 ... AWG 14)
Pick-off termi
-
nal blocks
Single conductor
connection
solid, finely
stranded:
0.5 ... 10 mm
2
(AWG 20 ... AWG 8)
Multiple conductor connection (only for conductors with the same
cross-section):
solid, finely
stranded:
max. 2 x 6 mm
2
(max. 2 x AWG 10)
Tightening
torque
Main terminals
6 - 8 Nm
Auxiliary con
-
tacts
0.4 Nm
Pick-off terminal
blocks
1.5 - 1.8 Nm
Wiring to terminal blocks: 63 A, UKH95 / USLKG95
Stripping length: 33 / 30 mm
Torque: 15 ... 20 Nm / 15 ... 20 Nm
Wiring to terminal blocks: 80 A, UKH150 / USLKG95
Stripping length: 40 / 30 mm
Torque: 25 ... 30 Nm / 15 ... 20 Nm