© 2021 Staheli West
100
Sensors
Sensor
Function/
Range
Normal
Range Warning
Trip/
Alarm
Connector
(Wire Harness End)
Flue Temperature
0-1000 F
300-450 F
550 F
600 F
DT06-4S
Boiler Water Temperature
0-300 F
100-240 F
DT06-4S
Furnace Door Temperature
0-300 F
100-150 F
160 F
180 F
DT06-4S
Ambient Temperature
0-300 F
100 F
DT06-4S
Feed Pump Protection
0-30 psi
>5 psi
while
pump is
running
<5 psi
(Shuts off
pump)
DT06-4S
Steam Pressure
0-30 psi
6-13 psi
DT06-4S
Supply Water Level
0-5 psi/
0-500
gallons
0-500
gallons <50 gallons
DT06-4S
Fuel Level
0-5 psi/
0-150
gallons
0-150
gallons <50 gallons
DT06-4S
0.5-4.5 V
Signal
5 V GND
0.5-4.5 V
Signal
5 V GND
0.5-4.5 V
Signal
5 V GND
0.5-4.5 V
Signal
5 V GND
4-20mA
Signal
4-20mA
Signal
4-20mA
Signal
12.00v
12.00v
12.00v
4-20mA
Signal
12.00v