04: Maximum charger current setting
Interface
Setting
Set up the maximum charger current.
1/2/4/6/8: setting the maximum charger current at 1/2/4/6/8
Ampere. (Default: 8A)
Note:
This setting is only effective for super charger.
06: Autonomy limitation setting
Interface
Setting
Parameter 2: Set up backup time on battery mode for general
outlets.
0-999: setting the backup time in minutes from 0-999 for general
outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note: When setting as “0”, the backup time will be only 10
seconds.
07: Battery total AH setting
Interface
Setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH. Please
set the correct battery total capacity if external battery bank is
connected.
08: EPO logic setting
Interface
Setting
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO logic, it
will activate EPO function with Pin 1 and Pin 2 in open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
00: Exit setting