2.6 Battery Replacement
NOTICE:
This UPS is equipped with internal batteries and only service personnel can replace the
batteries.
CAUTION!!
Consider all warnings, cautions, and notes before replacing batteries.
NOTE:
Upon battery disconnection, equipment is not protected from power outages.
Step 1
Step 2
Step 3
Step 4 Step 5 Step 6
Step Step 7
Step 1
: Remove front panel.
Step 2
: Disconnect battery wire and remove battery panel.
Step 3
: Pull out the battery box.
Step 4
: Remove the top cover of battery box and replace the inside batteries.
Step 5
: After replacing the batteries, put the battery box back to original location and screw in tightly.
Step 6
: Re-connect the battery wire and screw battery panel back on the unit.
Step 7
: Put the front panel back on the unit.