INSTALLATION 

Hazardous voltage. Can shock, burn or kill.

Do not lift pump by the power cord. See “Cord Lift Warning”
on Page 3.

NOTICE:

Install the pump on a hard, level surface (cement,

asphalt, or inside a sump basin, etc.). Never place the pump
directly on earth, clay or gravel surfaces.

Piping

Piping must not be smaller than pump discharge.

When installed in a 

sewage

system, the pipe must be capable

of handling semi-solids of at least 

2"

(51mm) in diameter.

The rate of flow in the discharge pipe must keep any solids
present in suspension in the fluid. To meet minimum flow
requirements (2 feet per second in the discharge line), size
the pipe as follows:

A Pipe Size Of:

Will Handle a Flow Rate Of:

1-1/2" (38mm)

12 GPM

2" (51mm)

21 GPM

2-1/2"(64mm)

30 GPM

3"(76mm)

48 GPM

In a 

sewage

system use a 

2"

(51mm) check valve in pump

discharge to prevent backflow of liquid into sump basin. The
check valve should be a free flow valve that will easily pass
solids. Be sure check valve installation complies with local
codes.

NOTICE:

For best performance of check valve when han-

dling solids, do not install it with the discharge more than 45°
above the horizontal. Do not install the check valve in a verti-
cal position as solids may settle in the valve and prevent it
from opening on startup.

Drill a 3/16" (5mm) hole in the discharge pipe about 1–2" 
(25-51mm) above the pump discharge connection (but below
check valve) to prevent airlocking the pump.

Electrical

Hazardous voltage. Can shock, burn, or kill.

When installing, operating, or servicing this pump, follow the
safety instructions listed below.

1.

DO NOT

splice the electrical power cord.

2.

DO NOT

allow the electrical cord plug to be submerged.

3.

DO NOT

use extension cords. They are a fire hazard and

can reduce voltage sufficiently to prevent pumping and/or
damage motor.

4.

DO NOT

handle or service the pump while it is connect-

ed to the power supply.

5.

DO NOT

remove the grounding prong from the plug or

modify the plug. To protect against electrical shock, the

power cord is a three-wire conductor and includes a 
3-prong grounded plug. Plug the pump into a 3-wire,
grounded, grounding-type receptacle. Connect the pump
according to the NEC or CEC and local codes.

For automatic operation, plug or wire the pump into an auto-
matic float switch or duplex controller. The pump will run con-
tinuously when plugged directly into an electrical outlet.

Connect or wire pump to its own individual branch circuit with
no other outlets or equipment in the circuit. Size fuses or cir-
cuit breakers according to the “Motor, Switch and Cord
Specifications” chart.

Risk of electrical shock and fire. Be sure

that power supply information (Voltage/ Hertz/Phase) on
pump motor nameplate matches incoming power supply
exactly. Install pump according to all electrical codes
that apply.

Explosion hazard.

Improper ventilation of

sewer gases can result in leakage of methane sewer gas,
and a possible explosion of fumes, resulting in severe injury
or death. Vent basin according to all local codes.

NOTICE:

Proper ventilation is needed to prevent negative

basin pressure and to provide air for proper aerobic activity
within the basin.

The sewage basin should be located at the lowest place in the
basement or area to be drained. Floor drains from other areas
in the basement may be tiled into the basin. Drain tile around a
house foundation may also be tiled into the basin, effectively
removing water and relieving pressure from this area.

Basin covers are used to exclude refuse from the basin.

NOTICE:

Read and understand this instruction manual

before your concrete floor is poured.

Installation Instructions. See Figure 1.

1.

Dig the hole for the sewage basin and the sub-base. The
hole must be deep enough so the finished floor is flush
with the top of the basin. Refer to Figure 1, Page 3.

NOTICE:

The sub-base should include 4" of sand or

gravel. The maximum diameter of crushed rock should be
1/2". The recommended maximum diameter of pea gravel
is 3/4".

2.

Level the sub-base out, until it is smooth. Sharp rock can
damage the basin.

3.

Install the basin on top of the sub-base.

4.

Backfill around the basin with crushed rock, with a maxi-
mum diameter of 1/2", or use pea gravel.

5.

Insert the 4" inlet pipe through the rubber grommet. Insert
it 2 inches into the basin. Dish soap can be used to lubri-
cate the rubber grommet. If necessary, file the sharp
edges of the pipe to prevent damage to the grommet.

NOTICE:

The pipe should pitch down to the basin inlet at

1/4" per foot. This will cause the water to run into the
basin.

6.

Lubricate the square cut O-Rings with dish soap. Insert
them into the groove on the bottom side of the flanged
grommets.

7.

Install the flanged grommets into the basin lid.

8.

Install the discharge pipe into the 2" FNPT discharge
grommet.

2

GPM AT TOTAL FEET

Model

5

10

15

20

25

30

CAPACITY GALLONS/MINUTE

SC550120T

120

90

45

18

SC440120T

90

66

25

18

No flow 

at height

shown below

*For performance at maximum temperature see Catalog.

PERFORMANCE

Содержание SP440120T

Страница 1: ...ee instructions under Service 7 Vent sewage or septic tank according to local codes 8 Do not install the basin or pump in any location classi fied as hazardous by the United States National Electrical...

Страница 2: ...wire pump to its own individual branch circuit with no other outlets or equipment in the circuit Size fuses or cir cuit breakers according to the Motor Switch and Cord Specifications chart Risk of el...

Страница 3: ...en the motor cools down the overload protector will automati cally reset and start the motor If the overload trips frequently check for the cause It could be a stuck impeller wrong low voltage or an e...

Страница 4: ...ble Lift off the stator 3 Remove the seal s ceramic seat from the shaft and tap the body of the seal out of the lower motor housing 4 Clean the seal cavity thoroughly before installing the new seal NO...

Страница 5: ...eller 1 PW5 11P 14 Volute 1 PW1 13 15 Automatic Float Switch 1 PS217 64 Switch Cord Clamp 1 CC0030 13 8 32 x 1 2 Capscrew 1 U30 539SS Dielectric Oil 1 U197 8A Not Illustrated REPAIR PARTS PUMP Key Par...

Страница 6: ...1 PW73 48 2B Sewage Basin Cover 1 PW73 60 3 Gasket Tape Cover 1 4 Sewage Basin 1 PW73 46 PW73 46 5 Inlet Hub Snap In 1 PW73 47 PW73 47 6 Discharge Pipe 1 U78 996P U78 997P 7A Sewage Pump 1 SC550120T 7...

Страница 7: ...ged 5 Check for blockage in pump inlet impeller check valve or discharge pipe 6 Disconnect the pump from the power source for a minimum of 30 minutes to allow the motor to cool and to protect yourself...

Страница 8: ...extra quick trip overload relays of recommended size are not used our warranty is void Buyer s only remedy and Sta Rite Industries only duty is to repair or replace defective products at Sta Rite Ind...

Страница 9: ...rvicio para la puesta a punto 7 Ventile el tanque s ptico o de aguas residuales conforme con los c digos locales 8 No instale el dep sito ni la bomba en ning n lugar clasificado como peligroso por el...

Страница 10: ...e en una toma de corriente el ctrica Es importante conectar o cablear la bomba a su propio ramal individual sin otro tomacorriente ni aparato conectado al circuito Determine el tama o de los fusibles...

Страница 11: ...ay una falla el ctrica en el motor haga que un experto en reparaciones lo revise La bomba tiene lubricaci n permanente No requiere aceite ni grasa MANTENIMIENTO Tensi n peligrosa Puede provocar choque...

Страница 12: ...la de la caja inferior del motor 4 Limpie bien la cavidad de la junta antes de instalar la nueva junta AVISO Aseg rese de que las caras de la junta est n limpias no raye ni da e la cara de la nueva ju...

Страница 13: ...ruptor autom tico de flotador 1 PS217 64 Abrazadera del cord n del interruptor 1 CC0030 13 Tornillo prisionero 8 32 x 1 2 1 U30 539SS Aceite diel ctrico 1 U197 8A No ilustrado PIEZAS DE REPARACI N BOM...

Страница 14: ...s 1 PW73 60 3 Cinta de empaque cubiertar 1 4 Dep sito de aguas residuales 1 PW73 46 PW73 46 5 Campana de admisi n a presi n 1 PW73 47 PW73 47 6 Tuber a de descarga 1 U78 996P U78 997P 7A Bomba de agua...

Страница 15: ...ue la admisi n de la bomba el impulsor la v lvula de retenci n o la tuber a de descarga no est n bloqueados 6 Desconecte la bomba de la fuente de corriente por un m nimo de 30 minutos para permitir qu...

Страница 16: ...paro extra r pido del tama o recomenda do nuestra garant a quedar anulada El nico recurso del comprador y la nica obligaci n de Sta Rite Industries ser n el de reparar o reemplazar los productos defec...

Отзывы: