Ashby-P Insert
24
Mobile Home Installation
Unit must be installed in accordance with the:
Manufactured Home and Safety Standard (HUD), CFR 3280, Part 24
Unit may be installed in a Mobile Home, after the initial sale of the Mobile Home, not for
Recreational Vehicles. The following installations are approved:
1.
In a Masonry Fireplace – The Masonry Fireplace must be built according to the requirements of
the
Standards of Chimneys, Fireplaces, Vents and Solid Fuel Burning appliances, N.F.P.A.
211
and any National, State or Local codes that apply.
2.
In a Zero Clearance Fireplace – The Factory built Zero-Clearance Fireplace and its Chimney must
be listed per UL 127 or ULC S610 standards.
3.
As a Zero Clearance Fireplace.
When building the unit in as a Zero-Clearance Fireplace, St.
Croix factory Built Cabinet, part # 80P53963, must be used.
Follow instructions on page 11.
Mobile home installations must observe the following:
1. WARNING: DO NOT INSTALL IN A SLEEPING ROOM.
2. WARNING: COMBUSTION AIR MUST COME FROM THE OUTSIDE OF THE MOBILE
HOME! FAILURE TO DO SO MAY CREATE NEGATIVE PRESSURE WITHIN THE
MOBILE HOME AND COULD DISRUPT PROPER VENTING AND OPERATION OF THE
PELLET STOVE.
3. CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOORS, WALLS, CEILING
AND ROOF MUST BE MAINTAINED.
4. Electrically ground the insert to the metal chassis of the home. Use a number eight, (8), gauge or
larger copper wire, (Y).
5. Maintain an effective vapor barrier at location where PL vent exits the structure.
6. Check any other local building codes or other codes that may apply.
7. Do no use components other than those specified for use with this unit.
8. Floor protection requirement must be followed precisely.
9. Approved Venting materials are Single Wall Stainless, Stainless Flex, PL Vent and Corn Vent.