Menu Manager Configuration Errors
Error
Description
Recommended Action
100
ADE: Configuration of the ADE
interface is invalid.
detected: Protocol Type, Dial Type, Unit Multiplier, Digital Input Function Type or Digital Output Func-
tion Type.
1.
is only allowed if number of dials is less than 8.
2.
The resolution of the totalizers (i.e. Unit Multiplier) must be set to something other than
OFF.
3.
. There are not
enough display digits to accommodate 8 dials and greater than 100 units of resolution.
4.
. There are not enough
display digits to accommodate 7 dials and greater than 1000 units of resolution.
101
ADE: Enabling/Disabling ADE
operation is invalid
This error is observed when Digital input or output function is manually selected for ADE operation.
Enabling or Disabling ADE operation can only be accomplished by setting the ADE protocol type.
110
Output 1/2: Pulse Output
Configuration Error
width or digital output function type for pulse output operation. Preparing these parameters for pulse
output operation (i.e. forward or reverse) has limitations that are monitored by the menu manager.
1.
2.
.e.
3.
The pulse frequency limit is 10 kHz when the pulse width is 0 (i.e. 50% duty cycle).
The pulse frequency limit is 1 / (2 * Pulse Width) when the pulse width is non-zero in order to achieve
a 50% duty cycle.
For AMR operation, the frequency limit is 3 HZ.
Follow these steps for configuring meter for pulse output operation:
1.
Set PPU to zero for both output 1 and 2
2.
3.
Set PW as required by equipment receiving pulse transmissions from meter. Observe
frequency limits for non-zero pulse widths.
4.
.e. 1000 HZ @ 250 GPM
5.
(i.e. 250 GPM / 500 GPM = 0.5)
6.
conversion factor = 1/3600, for GPS, conversion factor = 1
7.
* (conversion factor) ]= (1000 / 0.5) / [500 * (1/60) ] = 240 Pulse / Gallon
8.
frequency is within limits. Then redo steps 4-7
If not using the pulse outputs, set the pulses per unit to zero to allow for reconfiguration of the
full scale flow. If it is required to use the pulse outputs, re-evaluate the pulse output configuration.
Consider recording and clearing totalizers following pulse output configuration"
120
Display: Totalizer Conversion
Error – Totalizer cannot be prop-
erly converted for display
This error is observed while trying to change the totalizer units. Limits of display will prevent
. Consider
recording and cleaning totalizers prior to changing totalizer.
121
Output 1/2: Pulse Output
This error is observed when changing the totalizer units of measure. This error implies the pulse
. Please note the pulses per unit is not automatically
. The pulses per unit should be manually changed to
accommodate the desired units of measure. It may be necessary to set the pulses per unit to zero then
change to the desired totalizer units.
Installation & Operation Manual
Page 57
March 2014
Configuring the SSK513
as an ADE interface has the following limitations, Protocol Type V1