ADE INTERFACE
This feature requires firmware version 1.10 or later. Reference SSK P/N 6734-003 to obtain a firmware upgrade kit
.
Enabling the meter as an ADE register requires three settings, all within the advanced menu, to be configured.
•
Unit Multiplier – Selects the resolution of the display totalizer.
•
Protocol Type – Selects the type of information to be transmitted to the ADE transmitter.
•
Dial Type – Enables ADE and selects the number of significant totalizer digits to transmit.
Changing the dial type from Disabled will automatically configure the necessary digital inputs/outputs. It is not allowed to
manually change the digital inputs/outputs within the
Input/Outputs
menu.
Below is a wiring diagram for connecting an ADE
transmitter to the meter.
ADE Connections
1
2
3
4
5
6
7
8
9
10
11
12
13
14
IMPORTANT:
Remove jumper
JP1 before connecting transmitter
to meter
JP1
RED = CLOCK
GREEN = DATA
BLACK = GND
ADE Transmitter Cable
Output #1
COM
Input
Figure 20: ADE Interface
SSK
513
Electromagnetic Flow Meter
Page 52
March 2014