PROGRAMMING THE LEVEL SENSOR

 

The tank level sensor comes pre

-

programmed. However, the set points (Q1 –

 

SP1 and Q1 –

 

RP1) can be adjusted to 

configure the system specifically for the application. 

 

The level sensor displays the tank level as a percent (%) full. However, all parameters are measured in millimeters 
(mm) from the bottom of the probe. The usable range of the level sensor is between 10 mm and 410 mm from the 
bottom of the probe, a 400 mm range. 

 

There are two switching outputs that can be adjusted: Q1 and Q2. Output Q1 is used for the Auto

-

Refill feature and 

output Q2 is used for the Low Tank Level indicator. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To access the above parameters from the main display (% full), press and hold the 

Set

” 

button. Use the up and down 

arrows to navigate to 

Q1MENU

” 

or 

Q2MENU

” 

and press the 

Set

” 

button. Use the up and down arrows to navigate 

to 

SP1

” 

or 

RP1

” 

(or 

SP2

” 

and 

RP2

”) 

and press the 

Set

” 

button. Use the up and down arrows and the 

Set

” 

button 

to change the numeric values assigned to the given parameter. Instructions for setting other parameters can be found 
on pages 32

-

35 of the provided component manual.

 

Assuming the tank has been initially filled and given the values in the above table, as the system is being used the level 
in the tank will decrease. Once the fluid reaches 250 mm from the bottom of the probe, 63% full (100% * (250

-

10)/380=63%), Auto

-

Refill will turn on. As the fluid level rises and reaches 390 mm from the bottom of the probe, 

100% full, Auto

-

Refill will be turned off.

 

If Auto

-

Refill is switched off or the supply is interrupted, and the fluid level reaches 10 mm from the bottom of the 

probe, 0% full, the Low Tank Level indicator will turn on. This is intended as a warning that the system is not automati-
cally refilling. The Low Tank Level indicator will turn off once the fluid level rises above 50 mm from the bottom of the 
probe, 10% full. 

 

Menu

 

Parameter

 

Name

 

Description

 

Preset

 

Expert

 

Probe

 

Probe Length

 

Length of probe for this application

 

457 mm

 

Qa

 

QAHIGH

 

High Level 20ma

 

Maximum tank level (QAHIGH>QALOW)

 

380 mm

 

AutCal

 

  

  

  

  

Qa

 

QALOW

 

Low Level 4ma

 

Minimum tank level

 

10 mm

 

Qa

 

QAPOL

 

Configure

 

Analog output signal as configured

 

QA

-

Nrm

 

Qa

 

QATYP

 

Configure

 

Setting the output signal

 

Auto V

 

DspVal

 

Length

 

Configure

 

Display shows fill level in %

 

%

 

Q1

 

SP1

 

Switching Point 1

 

High Level 

-

 Auto

-

Refill stops filling

 

380

 

Q1

 

RP1

 

Reset Point 1

 

Low Level 

-

 Auto

-

Refill begins filling

 

76

 

Q1

 

OU1

 

Switching Function

 

Output Type 

-

 Normally Open/Closed

 

Qx

-

Hnc

 

Q2

 

SP2

 

Switching Point 2

 

Not Low Level 

-

 Indicator will turn off at or 

50

 

Q2

 

RP2

 

Reset Point 2

 

Low Level 

-

 Indicator will turn on at or below 

10

 

Q2

 

OU2

 

Switching Function

 

Output Type 

-

 Normally Open/Closed

 

Qx

-

Hno

 

Содержание AutoJet ES2500

Страница 1: ...AutoJet ES2500 Electrostatic Manifold System OWNER S MANUAL MI102012 000 spray com...

Страница 2: ...9 4 4 Operating Home Screen 9 4 5 Recipe Setup 10 4 6 System Configuration 10 4 7 CH1 Configuration 11 4 8 Motor Driver Information 12 4 9 Alarm Settings 12 4 10 Monitor IO Settings 14 4 11 Help Sett...

Страница 3: ...damage the system CAUTION Product process or environment can be damaged or be in danger if the instructions are not followed correctly ATTENTION Supplementary information for the user that draws atten...

Страница 4: ...e can penetrate skin and cause severe injury ATTENTION Always remember to carefully read the chemical manufacturer s labels follow SDS and all directions WARNING OF SHOCK HAZARD To reduce the risk of...

Страница 5: ...et surface The average final drop diameter produced by the Electrostatic Manifold is less than 10 microns 3 2 PRODUCT FEATURES AND SPECIFICATIONS The ES2500 Electrostatic Spray System consists of thre...

Страница 6: ...tio D1 D2 WHEEL AND PIVOT MOUNTED ENCODER Calculating the calibration constant K Factor pulses ft K PPR Wheel CIR ft SPECIFICATIONS Resolution PPR 1024 Output 5 26V push pull Input 5 26V Bore 5 8 holl...

Страница 7: ...uration settings PANEL POWER REQUIREMENTS Voltage 120VAC 3Ph Frequency 60Hz Current 20A max ELECTROSTATIC PANEL FEATURES 10 HMI Touch Screen display Customizable spray parameters Washdown rated Three...

Страница 8: ...when the motor is off and will be green while the motor is running Purge Clean This button brings up the system Purge Clean settings See the Purge Clean section for more information ES2500 Menu Whenev...

Страница 9: ...ilized when cleaning and flushing the system This is because the clean function does not activate the HV connection This allows water to flush the system Operators can set the flow rate for the clean...

Страница 10: ...individual recipe allows you to Create a name Enter the flowrate setpoint in gallons per hour GPH or based on mL per Sq Ft line speed Enter the Electrostatic voltage setpoint in kV Set the pump primin...

Страница 11: ...CH1 HV AMPERAGE FEEDBACK SETUP This screen allows the operator to set an amperage alarm if the amperage exceeds this amount the system will fault CH1 LEVEL SENSOR SETUP Relying on the input data from...

Страница 12: ...eful when troubleshooting the motor 4 9 ALARM SETTINGS The ES2500 system notifies operators of active and ongoing alarms at the top of the HMI screen and via stack light illu mination The Active Alarm...

Страница 13: ...tack Light serves as an easy visual indication for the current system status of the ES2500 The Stack Light fea tures three possible notification lights green amber and red The green and red lights can...

Страница 14: ...en below This screen provides live readings of both the analog and digital aspects of the PLC This screen can pro vide useful information when troubleshooting system components PLUGIN RELAY OUTPUT Thi...

Страница 15: ...ETTING Selecting Help from the navigation menu will bring up a screen that displays system information access the HMI OS Screen Map and change password profiles SCREEN MAP The Screen Map displays all...

Страница 16: ...ions 5 4 LEVEL SENSOR The level sensor sends a signal when the tank gets low to let the control panel know when to shut off the system to prevent the pump from running dry and becoming damaged The lev...

Страница 17: ...e tank will decrease Once the fluid reaches 250 mm from the bottom of the probe 63 full 100 250 10 380 63 Auto Refill will turn on As the fluid level rises and reaches 390 mm from the bottom of the pr...

Страница 18: ...the operator to be able to view the Electrostatic Manifold while at the control panel This will allow for easier adjustments and fine tuning of the electrostatic spray as the operator will be able to...

Страница 19: ...erfere with the electrostatic fields and skew the spray or potentially trip the AccuJet Electrostatic Controller All fluid must be run through a filter capable of removing 90 micron particulates HIGH...

Страница 20: ...rods on the electrostatic field The ground rods themselves can also be moved in ward to increase the effect ELECTROSTATIC VOLTAGE The ES2500 Manifold is rated to work with a voltage from 0 30 000V Thi...

Страница 21: ...connections are properly connected and secure 2 Ensure that the manifold is plumbed and positioned properly above the target 3 Verify that the manifold grounding wires are properly connected Ensure th...

Страница 22: ...DISASSEMBLY WARNING High Voltage Make sure that power has been disconnected to high voltage line before any attempt at disassembly STEP 1 The Manifold nozzles can be removed from the end mounts so the...

Страница 23: ...de should fall out Take note of how the electrode fits inside the bushing STEP 4 Remove the electrode and its gasket Then the through hole bushing should fall out STEP 5 Remove screws from underside o...

Страница 24: ...24 6 8 Electrostatic Manifold Diagram...

Страница 25: ...control panel Check HV cable connection between the system control panel and the manifold Verify trigger signal Check manifold for clogging 3 Air in liquid line poor pump performance Check for leaks C...

Страница 26: ...er pump adjustment Adjustment pump flow by changing the setting in the recipe Damaged or leaking lubricant lines Inspect identify and replace lines Clogged or leaking pump Clean or replace pump Clogge...

Страница 27: ...RM Problems with motor wiring Motor torque speed out of range Review and replace cables if dam aged Check operating conditions and settings specifically max flow Pump servicing may be required System...

Страница 28: ...ve companies Warranty is one 1 year on non wear parts from ship date Wear items are covered for manufacturing defect only for a period of one 1 year Wear items include but may not be limited to Liquid...

Отзывы: