Delay time
=10 s
Alarm delay reset
Alarm level
Alarm
activated
The effect of alarm delay
Alarm delay is set in steps of 2 seconds, to max. 600 seconds = 10 minutes. During the delay time,
the measured value has to be constantly above the alarm level, else the delay is interrupted and
measurement continued without triggering a relay or changing the status light. First after a full
delay period the relay is triggered.
Alarm is reset automatically when the alarm condition (high measured value) is terminated. There
is no manual reset.