
IM-P505-02-US
Issue 1
70
UTM20 Series Ultrasonic Transit-time Flowmeters
10.21 Information Menu
An asterisk (*) indicates the parameter default
Information Submenus
Options/Descriptions
VENDOR
BADGER METER
MODEL
UTM20
P.N.:
Badger Meter part number
S.N.
Serial Number
FW VERSION
Firmware Version xx xx xxx
CAL. DATE
Calibration Date YYYY-MM-DD
DATE CODE
Manufacture Date YYYY-MM-DD
TAG ID
16 characters
10.22 Diagnostics Menu
The DIAGNOSTICS menu displays system status and allows you to clear the history, reset to factory
defaults and reboot the system An asterisk (*) indicates the parameter default
Diagnostics
Submenus
Options/Descriptions
READINGS
SIGNAL STRENGTH
Read-only numeric with message to indicate the quality of the
ultrasonic signal
HISTORY
Chronological list of 120 past errors, alarms and warning
messages
DELTA TIME FILTERED
Read-only ##.## ns
FLOW RATE RAW
Read-only unfiltered flow rate
FLUID SOUND SPEED
Read-only; Units are the same as VELOCITY; Measured
ultrasound speed of the fluid
DELTA TIME RAW
Read-only ns
REYNOLDS NUMBER
Read-only; unitless
REYNOLDS FACTOR
Read-only; unitless
TEMPERATURE #1
Read-only; Energy meters only; Units are the same as the
Home Screen.
TEMPERATURE #2
Read-only; Energy meters only; Units are the same as the
Home Screen.
DELTA TEMPERATURE
The temperature difference between the two RTDs, either T1
- T2 or T2 - T1, according to the setting in INPUT/OUTPUT >
RTD > DELTA TEMP
TOTAL OVERFLOW
COUNT
Numeric integer
The TOTAL OVERFLOW COUNT
increments each time the flow total
exceeds the digits in the display
ENERGY OVERFLOW
Numeric integer
The ENERGY OVERFLOW is a
counter that increments each time
the energy total exceeds the digits
in the display