UTM20 Series Ultrasonic Transit-time Flowmeters
10.11 Setup > Inputs/Output > Output #1 (or Output #2 or
Output #3)
Output #1, Output #2 or Output #3 can operate independently as a frequency, totalizer pulse, direction
status or alarm status output In the SETUP > INPUT/OUTPUTS > OUTPUT #1 (OR OUTPUT #2 OR
OUTPUT #3) > MODE menu, select the MODE of operation Then go to the PARAMETERS menu to
set up the operation for that MODE
Output #3 is available on the energy unit only An asterisk (*) indicates the parameter default
Output #1 Submenus Options/Descriptions
MODE
*FREQUENCY
PULSE TOTAL
FLOW DIRECTION
ALARM
DISABLED
FREQUENCY and PULSE TOTAL modes are
not available with AUX OUTPUT #1 and #2 dry
contact output
PARAMETERS
(Frequency Mode)
OUTPUT
SOURCE
*FLOW RATE VELOCITY
ENERGY FLOW (Energy meter only)
TEST FREQUENCY
Select the reading to
assign to the frequency
output
VALUE AT
0 HZ
Numeric
entry Units
and decimal
place based
on parameter
selected
Negative
numbers
accepted Default
-5000
Enter the maximum flow rate or velocity
frequency that corresponds to maximum
frequency flow rate or velocity Can be negative
to indicate reverse flow The units of Maximum
match the units in
SETUP > MEASUREMENTS > FLOW UNITS
Example 1:
For a system that only has flow in one direction,
the maximum flow rate is 100 gal/min, and the
corresponding maximum frequency is 2000 Hz,
set up the parameters to:
Parameter
Value
Output Source
Flow Rate
Minimum
0 gal/min
Maximum
100 gal/min
Maximum Frequency
2000 Hz
Example 2:
For a system that flow is bidirectional, the flow
rate ranges from -100 gal/min to 100 gal/min
and the frequency at 100 gal/min is 2000 Hz,
set up the parameters to:
Parameter
Value
Output Source
Flow Rate
Minimum
-100 gal/min
Maximum
100 gal/min
Maximum Frequency
2000 Hz
With this setup at no flow, the frequency output
is 1000 Hz
MAX VALUE
Numeric entry
Units and
decimal place
based on
source selected
Negative
numbers
accepted Default
5000
MAX
FREQUENCY
Numeric entry
Units in Hz
Default 1 kHz
TEST
FREQUENCY
Available when TEST MODE is selected for OUTPUT SOURCE To
check the wiring to the control system or device, you can override
the frequency output with a fixed frequency