IM-P505-02-US
Issue 1
63
UTM20 Series Ultrasonic Transit-time Flowmeters
Communication Submenus
Options/Descriptions
ENDPOINT
Select the settings to match the BEACON/AquaCUE settings Only the flow
total selected for the Home Screen will be sent Energy totals are not supported
DIAL COUNT
7, *8, 9, 10
RESOLUTION
*OFF, 1, 10, 100, 1000, 10000, 0.1, 0.01, 0.001, 0.0001
PROTOCOL
*DISABLED
V1
V2
V3
When an ORION endpoint is
connected to the transmitter,
select the settings to match the
BEACON/AquaCUE settings Only
the flow total selected for the
Home Screen will be sent
V1 protocol does not support dial
counts above 7
BACNET/IP
(Shows only with card
installed for AUTODETECT
or CARD TYPE is set to
BACNET/IP.)
WEBSERVER
Note: WEBSERVER is READ ONLY
*ENABLED
DISABLED
CLIENT TIMEOUT 0 to 65,535 ms
DEVICE INSTANCE BACnet ID range: 0 to 99,999,999
DHCP
*DISABLED
ENABLED
IP ADDRESS
Numeric entry ### ### ### ### Enter a value from 1
to 255 for the first value and 0 to 255 for the remaining
values Option not available if DHCP is enabled
SUBNET MASK
Numeric entry ### ### ### ### Enter each value
from 0 to 255 Option not available if DHCP is enabled
GATEWAY
Numeric entry ### ### ### ### Enter a value from 1
to 255 for the first value and 0 to 255 for the remaining
values Option not available if DHCP is enabled
DNS PRIMARY
### ### ### ### Enter a value from 1 to 255 for the
first value and 0-255 for the remaining values It is not
recommended to use static IP address in the range of
169 254 0 0 to 169 254 255 255 because clients may
not be able to locate the DNS server
DNS SECONDARY
### ### ### ### Enter a value from 1 to 255 for the
first value and 0 to 255 for the remaining values It
is not recommended to use static IP address in the
range of 169 254 0 0 to 169 254 255 255 because
clients may not be able to locate the DNS server
PORT
Use SoloCUE if you need to change the UDP port
from the default setting:
*AUTO NEGOTIATION
10 Mbit HALF DUPLEX
10 Mbit FULL DUPLEX
100 MbIt HALF DUPLEX
100 Mbit FULL DUPLEX
ACCESS
WRITE/READ allows full access
RESET/READ allows you to read any, but only write to
Flow Total Reset (cannot set up meter)
*READ ONLY allows read only