80
-
2nd digit
2nd digit = 0
:
Overtorque is detected only during agreed frequency.
2nd digit = 1
:
Overtorque is detected during stop or during running except for DB.
3rd digit
3rd digit = 0
:
When overtorque is detected, “Over Torque OL3” blinks in the digital
operator and the operation continues.
3rd digit = 1
:
When overtorque is detected, “Over Torque OL3” displayed on the
digital operator and the inverter output is shut OFF. Fault contact
signal is output. (Treated as a fault)
Setting either Sn-20 to 22 to "OB" enables signal to be output at overtorque detection.
(8) Operation Mode Select 5 (Sn-08)
1st digit
(frequency reference input by RS-485 option card or inverter unit select)
Specify whether RS-485 option card (PA-M or PA-P) or inverter frequency reference
is used for operation.
1st digit = 0
:
RS-485 Option card frequency reference is accepted.
1st digit = 1
:
Frequency reference from inverter control circuit terminals or the digital
operator is accepted.
2nd digit
(RUN/STOP command input by RS-485 option card or inverter unit select)
2nd digit = 0
:
RS-485 option card RUN/STOP command is accepted.
2nd digit = 1
:
RUN/STOP command from inverter control circuit terminals or the
digital operator is accepted.
3rd, 4th digit
(RS-485 stopping method after communication error)
MOTOR
CURRENT
Cn-26
HYSTERESIS 10%
TIME
MULTI-FUNCTION OUTPUT SIGNAL
(OVERTORQUE DETECTION SIGNAL)
ON
ON
Cn-27
Cn-27