26
-
9. PERIPHERAL AND OPTIONS
9.1 AC REACTOR
When power capacity is significantly large compared to inverter capacity, or when the
power factor needs to be improved, externally connect an AC reactor.
7300PA 220V 30 ~ 125HP and 440V 40 ~300HP have built-in DC reactor as standard.
(When the power factor needs to be improved, externally connect an AC reactor).
220V 25HP and 440V 25HP, 30HP connect an optional AC reactor When the power factor
needs to be improved.
440V 350 ~500HP need to connect an AC reactor externally.
Table 8 AC REACTOR
Inverter AC
Reactor
Voltage
HP
Rated current (A)
Current (A) Inductance (mH)
Code NO.
25 72
90 0.12
3M200D1610102
30 88
90 0.12
3M200D1610102
40 117
120 0.09
3M200D1610111
50 144
160 0.07
3M200D1610269
60 167
160 0.07
3M200D1610269
75 212
240 0.044
3M200D1610285
100 288
360 0.026
3M200D1610307
220V
125 327
360 0.026
3M200D1610307
25 38
50 0.42
3M200D1610218
30 44
50 0.42
3M200D1610218
40 59
60 0.36
3M200D1610226
50 75
80 0.26
3M200D1610234
60 86
90 0.24
3M200D1610242
75 111
120 0.18
3M200D1610251
100 151
200 0.11 3M200D1610323
125 189
200 0.11 3M200D1610323
150 231
250 0.09 3M200D1610331
175 267
330 0.06 3M200D1610340
215 304
330 0.06 3M200D1610340
250 340
400 0.05 4M200D0010008
300 380
500 0.04 4M200D0020003
350 516
670 0.032
4M200D0030009
400 585
670 0.032
4M200D0040004
440V
500 732
800 0.025
4M200D0050000
Содержание 7300PA series
Страница 6: ... 4 PART I INSTALLATION MANUAL ...
Страница 35: ... 33 PART II OPERATION MANUAL ...