54
-
(10) Setting prohibit frequencies 1 to 3 (Cn-16 to Cn-18)
Set a setting prohibit frequency in units of 0.1 Hz. A set value of 0.0 Hz disables this
function.
If the setting prohibit frequency ranges overlap, set setting prohibit frequency 1 to 3
as shown below:
Cn-18
≦
Cn-17
≦
Cn-16
(11) Setting prohibit frequency range (Cn-19)
Set the range of setting prohibit frequency in units of 0.1 Hz. The range of the setting
prohibit frequency is determined as follows, depending on combinations with Cn-16
to Cn-18.
Cn-16 to Cn-18
-
Cn-19
≦
the range of the setting prohibit frequency
≦
Cn-16
to Cn-18
+
Cn-19
Note: Constant-speed operation is prohibited in the setting prohibit frequency range. Output
frequency does not jump during acceleration or deceleration, which is performed smoothly.
(12) Digital Operator Display Unit (Cn-20)
The setting unit of frequency references 1 to 8 and jog frequency reference depends
on the set value of operator display mode (Cn-20) as follows:
Cn-20
Setting / Reading Unit
0
Units of 0.01 Hz
1
Units of 0.01%
2 to 39
Set in the units of r / min (0 to 39999).
r / min = 120 x frequency reference (Hz) / Cn-20
(Set the number of motor poles in Cn-20)
40 to 39999
The position of decimal point is set by the value of the 5th digit of Cn-20.
Value of 5th digit = 0: Displayed as XXXX
Value of 5th digit = 1: Displayed as XXX.X
Value of 5th digit = 2: Displayed as XX.XX
Value of 5th digit = 3: displayed as X.XXX
A set value of 100% frequency is dewii6ned by the 1st digit to 4th digit of Cn-20.
Example 1: When the set value of 100% speed is 200.0, Cn-20 = 12000 is set.
100% speed is displayed as 200.0 at Cn-29 = 12000.
60% speed is displayed as 120.0
Example 2: When the set value of 100% speed is 65.00, Cn-20 = 26500 is set.
60% speed is displayed as 39.00 at Cn-20 = 26500.
INTERNAL
FREQUENCY
REF.
SETTING FREQUENCY REF.
Cn-19
SETTING PROHIBIT
FREQUENCY RANGE
Cn-16
SETTING PROHIBIT
FREQUENCY
Cn-17
SETTING PROHIBIT
FREQUENCY
Cn-18
SETTING PROHIBIT
FREQUENCY