(3) Operation status (Sn-03)
Passwords (Sn-03=0000 or 0101)
The ability to set or read the different groups of constants is determined by Sn-03 as shown
below.
DRIVE mode
PRGM mode
Sn-03
To be set To be monitored
To be set
To be monitored
0000
* 1
An, Bn
Sn, Cn
An, Bn, Sn, Cn
-
0101
* 2
An
Bn, Sn, Cn
An
Bn, Sn, Cn
*1
:
Factory setting
*2
:
When in DRIVE mode, the parameter group Sn-, Cn- can only be monitored if the
RESET
key and the
DSPL
key are to be pressed at the same time.
*3
:
After a few trial operation and adjustment, the setting value Sn-03 is set to be “ 1111” so as
not be modified again.
Constants Initialization (Sn-03=1110 or 1111)
Except the parameter of Sn-01~02, the parameter groups of An-
□□
, Bn-
□□
, Cn-
□□
, Sn-
□□
and On-
□□
can be initialized as factory setting. At the same time, the terminal 5~8
can be set as 2-wire or 3-wire operation mode under different setting of Sn-03, please see
2-/3-wire operation mode on page 85.
Special mode (Sn-03=1010)
The order parameters On-
□□
can be set and read when setting Sn-03=1010, after
changing or monitoring any of the On-
□□
parameters, please set Sn-03=0000 or 0101.
Initialize the contents of monitoring parameter Un-11 and Un-12 (Sn-03=1000 and 1001)
The motor elapsed run hours (Un-11) and motor elapsed energy KWHR (Un-12)
can be reset by Sn-03=1000 and 1001 individually.
The LCD display (English) as below.
Sn-03 setting
LCD Display
0000
Sn-03=0000
Allow Setting
0101
Sn-03=0101
Inhibit Setting
1110
Sn-03=1110
2-Wire Initialize
1111
Sn-03=1111
3-Wire Initialize
1000
Sn-03=1000
Reset Un-11
1001
Sn-03=1001
Reset Un-12