(10) Monitor No. after Turning On Power Supply (Bn-10)
Data to be monitored after turning ON power supply is selected with constant No. in the form
of Un-
□□
.
○
1 Frequency reference
(Bn-10=01 — Display: Freq. Cmd)
○
2 Output frequency
(Bn-10=02 — Display: O/P Freq.)
○
3 Output current
(Bn-10=03 — Display: O/P I)
○
4 PID detected value after display unit changing
(Bn-10=04 — Display: PID Det. Value). ref to page 47.
(11) Multi-function Analog Output A01 Gain (Bn-11)
(12) Multi-function Analog Output A02 Gain (Bn-12)
Multi-function Analog Output A01 and A02 can be set for their individual voltage level
respectively.
Fig.10 Diagram of Multi-function Analog Output
(13) Detected Value Adjusting Gain (Bn-13)
The detected feedback value can be adjusted by multiplying adjusting gain Bn-13.
(14) Proportional Gain P (Bn-14)
Output P is obtained by multiplying deviation value by proportional gain Bn-14. No P
operation when Bn-14=0.0. Refer to page 45, the block diagram of PID control section.
(15) Integral Time I (Bn-15)
Output I is an integral value of deviation. The additional value obtained at every 7 msec can
be calculated by the following equation:
7 msec
(Deviation x ———————— )
Bn-15 set value
No I operation when Bn-15 = 0.0 sec. Refer to page 45, the block diagram of PID control
section.
Multi-function Analog Output A01
(Output contents depend on Sn-26)
10.0V × Bn-11,Bn-08
Terminal A01
Multi-function Analog Output A02
(Output contents depend on Sn-27)
10.0V × Bn-12,Bn-09
Terminal A02
Monitor items
Bias(Bn-08 or Bn-09)<0.0%
Bias(Bn-08 or Bn-09)>0.0%
Gain(Bn-11or Bn-12)>1.00
Gain(Bn-11or Bn-12)=1.00
Bias (Bn-08 or Bn-09)=0.0%
Output voltage
0% 100%
10V
0V