Installing the Detector
Alarm BIT
•
Yes
: Successful Manual BIT activates the Alarm
Relay for approximately 3 seconds (default).
•
No
: Successful Manual BIT does not activate the
Alarm Relay.
Auxiliary BIT
•
Yes
: Successful Manual BIT activates the
Auxiliary Relay for approximately 3 seconds
(default).
•
No
: Successful Manual BIT does not activate the
Auxiliary Relay.
EOL
*
•
Yes
: Auxiliary relay is used as End-of-Line.
•
No
: Auxiliary relay operates in accordance with
Functions 2 and 5 (default).
Only available in Models 40/40R-4XXXX and 5XXXX
3.8.4
Heated Optics
The heated optics can be defined as one of the following modes:
•
Heated Mode
•
Off
: Not operated
•
On
: Continuously
•
Auto
: Per temperature change
In Auto mode, the default Heat On setting is 41°F/5°C. Heating stops when the
temperature is 27°F/15°C above the start temperature.
You can define the start temperature below which the window will be heated. The
temperature can be defined between 32
–
86°F / 0
–
30°C.