Product Overview
2.4.5.3
SIL-2 (TÜV)
The 40/40R Opti10
cal Flame Detector is certified for the SIL-2 requirement per IEC 61508.4,
Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0
–
20mA current loop.
Or
•
Alert signal via alarm relay and fault relay
•
For more details and guidelines for configuring, installing, operating, and
service, see
on page 79 and
TÜV Report No. 968/EZ -
348.04/16
.
2.4.5.4
EN54-10
The 40/40R Flame Detector is certified to EN54-10 and CPD.
•
The detector is listed as Class 1 for sensitivity setting 15.
•
The detector has been tested and approved per EN54-10 by VdS.
•
This test includes a functional test, environmental test, EMI/EMC test, and
software check.
•
For more details see
VdS Report No. BMA 13110
.
2.4.5.5
Inmetro (UL)
The 40/40R Flame Detector is in compliance with the standards ABNT NBR IEC
60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC 60079-7, ABNT NBR IEC
60079-18, ABNT NBR IEC 60079-31, and INMETRO decree No. 179 as of May
18th, 2010. Further details may be found on Certificate of Compliance No. UL-BR
16.065XX.
2.4.5.6
TR CU/EAC
The 40/40R Flame Detector is in compliance with the standard TR CU 012/2011
per:
1Ex d e IIC T5 Gb X
Ex tb IIIC T96°C Db X
–
55°C
≤
Ta
≤
+75°C
Or
1Ex d e IIC T4 Gb X
Ex tb IIIC T106°C Db X
–
55°C
≤
Ta
≤
+85°C.
For more details, see
TR CU certificate No. ТR CU C
-
US.МЮ62.В.04333.