Specifications
54
SharpEye™
Single IR Flame Detector User Guide
A.2
Electrical Specifications
Table 18: Electrical Specifications
Operating
Voltage
Status
All
Outputs
Without
0
–
20mA
Power
Consumption
(Max. 24VDC)
Normal
1.61W
1.56W
Normal when heater on
2.28W
2.16W
Alarm
2.64W
2.28W
Alarm when heater on
3.24W
2.88W
Maximum Current
(Max. 24VDC)
Normal
70mA
65mA
Normal when heater on
95mA
90mA
Alarm
110mA
95mA
Alarm when heater on
135mA
120mA
Power
Consumption
(Max. 18
–
32VDC)
Normal
1.95W
1.85W
Normal when heater on
2.56W
2.45W
Alarm
3.04W
2.56W
Alarm when heater on
3.68W
3.2W
Maximum Current
(Max. 18
–
32VDC)
Normal
90mA
85mA
Normal when heater on
105mA
100mA
Alarm
130mA
115mA
Alarm when heater on
160mA
145mA
A.2.1
Electrical Input Protection
The input circuit is protected against voltage-reversed polarity, voltage
transients, surges, and spikes according to MIL-STD-1275B.
A.3
Outputs
A.3.1
Electrical Interface
There are 5 output wiring options. These options are defined at the factory per
the customer order and cannot be changed at the customer facility.
General Instructions for Electrical Wiring
on page 61 for the wiring/terminal
diagram for each option.
Unless otherwise specified, the default is option 1. The wiring arrangement is
identified on the detector by the part number (see
on page 16).
•
Option 1
: Power, RS-485, 0
–
20mA (Sink), Fault I Relay (N.C.), Alarm Relay,
(N.O.) (see Figure 6).
•
Option 2
: Power, RS-485, 0
–
20mA (Source) and HART protocol, Fault Relay
(N.O.), Alarm Relay, (N.O.), (N.C.).