Specifications
Appendix A:
Specifications
A.1
Technical Specifications
Spectral Response
Three IR Bands
Detection Range
(at highest
sensitivity setting
for 1ft
2
/0.1m
2
pan
fire)
Fuel
ft/m
Fuel
ft/m
n-Heptane
50/15
Kerosene
37/11
Gasoline
50/15
Methane
*
29.5/9
LPG
*
43/13
Ethanol 95%
25/7.5
Diesel Fuel
37/11
Methanol
25/7.5
JP5
37/11
IPA (Isopropyl
Alcohol)
25/7.5
Polypropylene
Pellets
37/11
Office Paper
20/6
30”/0.75m high, 10"/0.25m width plume fire
Response Time
Typically 5 seconds
Adjustable Time
Delay
Up to 30 seconds
Sensitivity Ranges
2 ranges for 1ft
2
/0.1m
2
n-heptane pan fire from
15ft/5m to 50ft/15m
Fields of View
Horizontal 90
, Vertical 90
Built-In-Test (BIT)
Automatic (and Manual)