GB
14
Proceed as follows for editing the parameters:
• Go to level 8 in the service menu using the + / - setting keys,
[ P A r ] appears
• Press Enter, [ P 0 0 0 ] appears. That is the parameter no. 000.
• Use the menu keys to go to the desired parameter.
• Press Enter and the current setting value of the parameter appears
• The value can be edited using the adjustment keys + / -.
• To confirm, press Enter
• Press the ESC key at the top left 3 times to return to the home position
Note:
the service menu stays open for 30 minutes. If you exit the service
menu in this time and then return to level 8 again, the password query is
omitted and you can access directly.
There is a separate list for the parameters and their function in the Appen-
dix at the end of this instruction. Several parameters are dependent on
each other. Therefore, always contact the customer services before making
changes.
Level 9: Digital inputs
Once the service menu has been activated (see level 7), in level 9 you can
query the status of the digital inputs. The allocation is as follows:
i01:
Digital input for the safety temperature limiting device
i02:
Wire jumper
i03:
Open
i04:
Open
F02:
Flue gas fan rotational speed (only in combination with a Hall- IC
speed sensor, not relevant here)
Proceed as follows for viewing the status:
• Go to level 9 in the service menu using the + / - setting keys,
[ d i n ] appears
• Press Enter, [ i 01 ] appears. That is the digital input 01.
• Use the menu keys to go to the desired parameter.
• Press Enter and the current setting value of the parameter appears
• The value can only be read and not edited
• To confirm, press Enter
• Press the ESC key at the top left 3 times to return to the home position
The digital input i01 must be at OFF. If it is at On then the STB has triggered
and has not (yet) been reset.
Level 10: Analogue inputse
Once the service menu has been activated (see level 7), in level 10 you can
query the status of the analogue inputs. The allocation is as follows:
t03:
Thermocouple 1 type K, current flue gas temperature in °C
t04:
Thermocouple 2 type K, not used
t01:
NTC 1 sensor, current room temperature in 1/10 °C,
thus, a display of 214 means 21.4°C
t02:
NTC 2 sensor, not used
t05:
NTC 3 sensor, not used
F01:
External analogue signal, not used
PreS:
Internal pressure sensor
Proceed as follows for viewing the status:
• Go to level 10 in the service menu using the + / - setting keys,
[ A i n ] appears
• Press Enter, [ t 03 ] appears. That is the snalogue input 03.
• Use the menu keys to go to the desired parameter.
• Press Enter and the current setting value of the parameter appears
• The value can only be read and not edited
• To confirm, press Enter
• Press the ESC key at the top left 3 times to return to the home position