Form 43343110
May 2021
-53-
20.0)
REPLACING PARTS
Only use genuine Space-Ray replacement parts. Parts are available from the factory for replacement by a
licensed person. Refer to the Replacement Parts Guide in Section 22.0) for all replacement parts.
20.1)
REMOVAL OF MAIN BURNER AND ELECTRODES
The main burner can be inspected without removing the burner housing from the heat exchanger tube.
1.
Disconnect electrical supply and Remove cover 1.
2.
Remove screw securing burner casting to the gas manifold.
3.
Disconnect Spark lead and sensing wire.
4.
Pull burner forward from the gas manifold and then out through the side of the box as shown.
5.
Check that the
spark gap is 1/8” between the electrode and the bu
rner casting as shown. Spark electrode
should be clean and free from debris.
6.
Flame sensor should be clean and free from debris.
7.
Check ceramic on the spark electrode, for replacement into the box the spark e
lectrode is the ¼” terminal
which connects to the spark lead.
8.
Check ceramic on flame sense electrode, for replacement into the box the flame sense electrode is the
3/16” terminal which connects to the violet wire. (in som
e models t
he terminal is ¼” pa
inted violet)
Содержание PCA-SS 100
Страница 13: ...Form 43343110 12 May 2021 7 1 DIMENSIONS STRAIGHT CONFIGURATION 48 HANGING CENTERS...
Страница 14: ...Form 43343110 May 2021 13 7 2 HEATER ASSEMBLY JOINING OF TUBE SECTIONS...
Страница 21: ...Form 43343110 20 May 2021...
Страница 48: ...Form 43343110 May 2021 47 19 0 TROUBLESHOOTING GUIDE SINGLE STAGE N5 L5...
Страница 49: ...Form 43343110 48 May 2021 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Страница 50: ...Form 43343110 May 2021 49 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Страница 51: ...Form 43343110 50 May 2021 19 1 TROUBLESHOOTING GUIDE TWO STAGE N7 L7...
Страница 52: ...Form 43343110 May 2021 51 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...
Страница 53: ...Form 43343110 52 May 2021 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...
Страница 55: ...Form 43343110 54 May 2021 20 2 REMOVING GAS VALVE AND MANIFOLD ASSEMBLY 20 3 AIR SWITCH PRESSURE CHECK...