ATTACHING BURNER BOX ASSEMBLY 

1.

 

Attach the burner box and gasket to end of tube flange and secure with 1/4-20 locknuts.  

2.

 

Assemble the optional end reflector flush with the end of the main body reflector.  Secure by sliding speed 
clips  onto  the  reflector  edges.    Evenly  space  the  speed  clips  on  the  sides  (one  each  side)  and  top  (two 
required) of the reflectors to provide a snug fit.  Leave a 3" space between the end reflector and the burner 
box assembly. 

3.

 

The heater can be mounted horizontally or at an angle of 30 degrees maximum from horizontal. 
When angle mounting, the burner box unit must be positioned upright as shown below Failure to install the 
control box in an UPRIGHT 

position will VOID the manufacturer’s warranty

 

 

Important:  NEVER  reuse  a  coupling..  Always  install  a  new  coupling  only  and  torque  as  per  instructions  above  and  the 
diagrams below. 

Содержание PCA-SS 100

Страница 1: ...a neighbor s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department DO NOT store or use gasoline or other flammable vapors and liquids in the v...

Страница 2: ...ir for Combustion Horizontal Through a Sidewall 40 15 2 Air for Combustion Through Ceiling 41 15 3 Air for Combustion hog barn 43 16 0 Lighting and Shutdown Instructions 44 17 0 Sequence of Operation...

Страница 3: ...Where unvented heaters are used gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1 000 Btu hr input of installed heaters Never use the heater as a support for a l...

Страница 4: ...at least half of every stall area be covered with a heater Straight Configuration Only Since straight tube heaters are always hotter at the control end than at the flue terminal end always observe the...

Страница 5: ...m Clearances to Combustibles listed in the manual and on the heater at all times NOTE 1 The clearances specified above must be maintained to combustibles and other materials that may be damaged by tem...

Страница 6: ...dentification Control Option Suffix Gas Type Description N5 Natural Single Stage Gas Valve Single Stage Input L5 Propane Single Stage Gas Valve Single Stage Input N7 Natural Two Stage Gas Valve Modula...

Страница 7: ...own 1 3 42907040 Control Fastener Kit comprising of 1 02189020 Screw 10 x 1 2 Self Drill TEKS 4 02167010 1 4 20 Locknuts 3 4 42921000 Tube Flange Gasket 1 5 43341000 Head End Reflector Kit includes 2...

Страница 8: ...zed Steel Aluminized Steel PCA SS 125 30 L5 PCA SS 125 30 N5 Propane Natural 30 ft 30 ft Aluminized Steel Aluminized Steel PCA SS 125 40 L5 PCA SS 125 40 N5 Propane Natural 40 ft 40 ft Aluminized Stee...

Страница 9: ...2100 10 Ft Tube less Flanges 1 2 3 4 3 43319100 Reflector 9 11 2 3 4 5 4 30462980 Tube Coupling 1 2 3 4 see below Hanger Kit Components 1 1 1 1 HANGER KIT COMPONENTS Item No Part No Description Qty 20...

Страница 10: ...TY 1 8 18 x Self Drilling Screws 02189030 QTY 2 C Fresh Air Inlet Through Ceiling Package Part 44129500 Contains a 4 Air Intake Assembly 44129000 QTY 1 b 4 x 30 Flexible Hose 30675020 QTY 1 c 4 Screw...

Страница 11: ...Relay Board Part 44195000 Contains Relay Board 30709058 QTY 1 Enclosure 30709059 QTY 1 Cord Connector 30635040 QTY 2 G 4 Vent Cap Part 30297040 for use on heater VENTED H 4 Flue Collar Adapter Part 30...

Страница 12: ...5 20 Ft 30 Ft 5 PCA SS 100 30 Ft 40 Ft 3 PCA SS 125 30 Ft 40 Ft 6 When installing a Defender series heater into a barn with stalls or partitions we recommend using a model that is no longer than 40 ft...

Страница 13: ...Form 43343110 12 May 2021 7 1 DIMENSIONS STRAIGHT CONFIGURATION 48 HANGING CENTERS...

Страница 14: ...Form 43343110 May 2021 13 7 2 HEATER ASSEMBLY JOINING OF TUBE SECTIONS...

Страница 15: ...manually crimped closed by the installer 4 When using rigid means for heater suspension rod flat bar etc provide sufficient lengths or swing joints to compensate for expansion See Figures b and c 5 He...

Страница 16: ...r level and result in lower tube temperatures when compared to horizontal mounting Angle mounting of straight tubes for spot or area heating e g where a single heater is used for space heating is not...

Страница 17: ...er box must be connected directly to the 12 radial hole flange of the 10 ft aluminized steel starting body section 4 Assemble a wire hanger with clamps from the end of the heat exchanger tube having t...

Страница 18: ...following coupling tightening instructions MUST be followed properly to ensure the integrity of the tube connections Two 10 self drilling screws MUST be installed at every coupling as shown in the in...

Страница 19: ...e tubes in the coupling 8 Check to ensure that the hardware is completely closed and the band is seated on the reaction block and interference pins as illustrated above 9 Once all the heater body sect...

Страница 20: ...e retainers to the tube using a spring provided with the heater as shown in Detail A Note The first reflector overlap must be able to slide for natural expansion and contraction of the heater when in...

Страница 21: ...Form 43343110 20 May 2021...

Страница 22: ...h side and top two required of the reflectors to provide a snug fit Leave a 3 space between the end reflector and the burner box assembly 3 The heater can be mounted horizontally or at an angle of 30...

Страница 23: ...w TISS wire assembly PN 44176510 spring and spring retainer clamp not included must also be installed Instructions 1 Make sure that the gap between the burner box and end of reflector is 3 and the ref...

Страница 24: ...embly to end of reflector at overlap joint Slide spring retainer clamp over end of reflector as shown Step 3 4 After attachment of the TISS check to make sure that there is sufficient tension on the w...

Страница 25: ...clamp must first be re positioned as shown using the bottom hole pattern of the clamp Follow procedures described earlier for all other adjustments Step 5 Failure to re position the wire clamp at the...

Страница 26: ...t a CSA or U L approved flexible connector supplied with this heater is required for connections between the rigid piping and the heater A union should be installed before the burner box inlet An appr...

Страница 27: ...stallation in US only The gas connector is 36 long and 1 2 nominal ID and must be installed as shown above in one plane and without sharp bends kinks or twists CANADA ONLY A Type I hose connector shou...

Страница 28: ...l electrical power to the system to connect manometer hoses 2 Turn the pressure test screw 3 32 Hex in the center of the boss not more than one turn counterclockwise Attach a 5 16 hose and manometer o...

Страница 29: ...Energize main gas valve solenoid as well as the HI terminal 4 Remove regulator cover screw from the high outlet pressure regulator see Figure 2 below and turn screw clockwise to increase pressure or c...

Страница 30: ...t switch 4 The power supply to the unit should be protected with a fused disconnect switch or circuit breaker A service switch as required by local codes shall be located in the vicinity of the heater...

Страница 31: ...NTROLS INTERNAL CONNECTION WIRING DIAGRAM SINGLE STAGE CONTROLS SCHEMATIC WIRING DIAGRAM IGNITION MODULE TERMINAL DESIGNATIONS 24VAC R 24 VAC Supply to Module TH W Thermostat Input PS W Pressure Switc...

Страница 32: ...343110 May 2021 31 SINGLE STAGE CONTROLS THERMOSTAT WIRING DIAGRAMS SINGLE STAGE CONTROLS I LINE VOLTAGE 120V THERMOSTAT CONNECTIONS SINGLE HEATER J LINE VOLTAGE 120V THERMOSTAT CONNECTIONS MULTIPLE H...

Страница 33: ...24V THERMOSTAT CONNECTIONS SINGLE HEATERS L LOW VOLTAGE 24V THERMOSTAT CONNECTIONS MULTIPLE HEATERS utilizing a fan center relay M 9 TWO STAGE N7 L7 INTERNAL AND THERMOSTAT CONNECTIONS TWO STAGE CONT...

Страница 34: ...ITION MODULE TERMINAL DESIGNATIONS 24VAC R 24 VAC Supply to Module TH W Thermostat Input PS W Pressure Switch Input GND System Ground V1 Valve Power V2 Valve Ground L1 120 240 VAC Input Hot IND Blower...

Страница 35: ...Form 43343110 34 May 2021 A LOW VOLTAGE 24V THERMOSTAT CONNECTIONS SINGLE HEATERS B LOW VOLTAGE 24V THERMOSTAT CONNECTIONS MULTIPLE HEATERS...

Страница 36: ...approximately 10ft from side of the heater as shown in Figure 1 and at distances from burner box as shown in chart of Figure 2 below Ideally this should also be located between the feed and drink line...

Страница 37: ...nder series heater into a barn with stalls or partitions we recommend using a 40 ft unit or shorter This is due to the natural characteristic of all tube heaters Which is they have a significant tempe...

Страница 38: ...0 75 PCA SS 100 40 35 40 65 PCA SS 125 30 60 50 75 PCA SS 125 40 50 40 65 PCA SS 125 50 40 30 55 PCA SS 150 40 60 50 75 PCA SS 150 50 50 40 65 Note 1 Vent lengths shown in the table are for horizontal...

Страница 39: ...protected as specified in the National Fuel Gas Code or the authority having jurisdiction 8 Single wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass th...

Страница 40: ...gas utility meters regulators relief valves or other equipment Building materials should be protected from flue gases and condensate Less than 18 0 45m when directly below a combustible overhang 8 In...

Страница 41: ...stion air can be brought directly to the heater by a 4 diameter duct field supplied less than 20 ft long or equivalent An approved vent cap and 4 flexible hose supplied in accessory Kit 44129510 must...

Страница 42: ...mbustion air duct Avoid locating the outside combustion air duct directly above the control box Provide a capped cleanout T as necessary The Cold Air Stopper supplied as accessory is installed into th...

Страница 43: ...resh air intake start collar instead of the flexible air intake hose as shown above 1 Remove the fresh air intake from the burner control unit shown in Step A 2 Press the cold air stopper into the fre...

Страница 44: ...ng air intake above curtain walls as they can leak When curtain walls are present use 4 inch light gauge PVC air intake material from curtain sidewall to the heater do not exceed 25 feet With an elbow...

Страница 45: ...o lockout and the valve relay will be de energized immediately The blower will be turned off following a post purge period of approximately 30 seconds 5 If the heater does not light manually reset the...

Страница 46: ...e is not re established the heater will go to lockout 17 1 SEQUENCE OF OPERATION TWO STAGE N7 L7 The chart below shows the sequence of operation for the normal operating cycle of the heater N7 L7 when...

Страница 47: ...f damage fatigue or corrosion If there are any signs of damage to the gas connection or leaks found in the gas piping immediately stop using the heater until the gas pipe and connections have been rep...

Страница 48: ...Form 43343110 May 2021 47 19 0 TROUBLESHOOTING GUIDE SINGLE STAGE N5 L5...

Страница 49: ...Form 43343110 48 May 2021 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...

Страница 50: ...Form 43343110 May 2021 49 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...

Страница 51: ...Form 43343110 50 May 2021 19 1 TROUBLESHOOTING GUIDE TWO STAGE N7 L7...

Страница 52: ...Form 43343110 May 2021 51 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...

Страница 53: ...Form 43343110 52 May 2021 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...

Страница 54: ...the gas manifold 3 Disconnect Spark lead and sensing wire 4 Pull burner forward from the gas manifold and then out through the side of the box as shown 5 Check that the spark gap is 1 8 between the el...

Страница 55: ...Form 43343110 54 May 2021 20 2 REMOVING GAS VALVE AND MANIFOLD ASSEMBLY 20 3 AIR SWITCH PRESSURE CHECK...

Страница 56: ...n series with the ground lead as shown in the diagram Connect the meter as follows Connect the black negative meter lead to the electronic control FC terminal Connect the red positive meter lead to th...

Страница 57: ...bustion blower will power off following the post purge period Fault Conditions Error Mode LED Indication Internal Control Failure Steady On Air Flow Fault 1 Flash Gas valve failure stuck open 2 Flashe...

Страница 58: ...Hinged SS solid 1 11b 02201070 Hinge 1 1 2 x 6 2 12 44140056 Access Panel LH burner end SS with sight hole 1 13 44140099 Access Panel RH burner end SS solid 1 14 4414006x Combustion Air Plate see size...

Страница 59: ...h for Two stage 1 47 42398150 Monitoring Light Red air switch operation 1 48 30186260 Air Switch set point 65 WC BLUE LABEL models 75 1 48a 30186240 Air Switch set point 75 WC PINK LABEL models 100 1...

Страница 60: ...s and can be purchased at any local hardware store 2 Please order by PART NUMBER not by Item Number 3 Replacement Part Prices are available when ordering 4 Please refer to complete Model Number when o...

Страница 61: ...Form 43343110 60 May 2021 23 0 WARNINGS CARD Copies of this card may be ordered at no charge under part no 43344990 for installation near the heater...

Страница 62: ...IED WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF WITHOUT LIMITING THE FOREGOING THE MANUFACTURER EXPRESSLY EXCLUDES ANY AND ALL IMPLIED WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WA...

Отзывы: