26
10.6 Day correction
Menu 5.6
parallel translation of the characteristic
The day correction produces a parallel translation of the heating
characteristic during the daytime operating hours, since depending on the
outdoor temperature it is possible that the building may not be optimally
heated with the set characteristic. If the characteristic is not optimised, the
following situation may occur:
in hot weather - the spaces are too cold
in cold weather - the spaces are too hot
In this case, one should gradually reduce the characteristic slope in steps
of 0.2, each time raising the day correction by 2-4 °C.
This procedure can be repeated several times as needed.
Setting range: from -10°C to 50°C / default setting: 5
10.7 Night correction
Menu 5.7
parallel translation of the characteristic
The night correction produces a parallel translation of the heating
characteristic during the nighttime operating hours. If a negative value
is set for the night correction, the reference
fl
ow temperature is lowered
accordingly during the nighttime operating hours. In this manner, primarily
at night, but also during the day when no-one is at home, the room
temperature is lowered, thus saving energy.
Example: A day correction of +5°C and a night correction of -2°C produces
a reference
fl
ow temperature in nighttime operation that is 7°C lower.
Setting range: from -30°C to 30°C / default setting: -2°C
10.8 Comfort temperature boost
Menu 5.8
parallel translation of the
characteristic
The comfort temperature boost is added to the set day correction. In this
manner it is possible to carry out quick heating and/or a higher temperature
in the living spaces at a certain time each day.
Setting range: from 0°C to 15°C / default setting: 0°C = off
Settings
Menu 5
10
10
10. Settings
(continued)
10.9 Low-rate period boost
Menu 5.9
parallel translation of the characteristic
The low-rate period boost is added to the set day correction. In this manner
it is possible, for example, to ensure greater buffer or heating circuit heating
during the low-rate periods.
Setting range: from 0°C to 15°C / default setting: 0°C = off
Speci
fi
cation of the operating times for the previously set values
(10.6-10.9) is described in greater detail under 8.2-8.4.