20
Times
Menu 3
8
8
8. Times
(continued)
8.5 Domestic hot water enable
Menu 3.5
The controller automatically switches off the domestic hot water
heating during the times that are not con
fi
gured.
Caution
8.4 Heating for low-rate period
Menu 3.4
This menu can be used to select a time range for each day of the week in
which the heating circuit is supplied with an increased temperature, e.g.
during low-rate periods of the power utility. Especially in systems with a
buffer storage tank, the heat retained from the low-rate periods can then be
retrieved via the heating circuit later, thus saving lower operating costs.
Setting range: One time range for each day of the week
Default setting: Mon-Sun off
Note: See 10. for the associated temperature settings
This menu is used to select the enable times for the domestic hot water
heating; two time periods can be speci
fi
ed for each weekday and copied
over to the following days.
Setting range: Two time ranges for each day of the week
Default setting: Mon-Sun 06:00-22:00
Note: See 10. for the associated temperature settings
8.6 Domestic hot water for low-rate period
Menu 3.6
This menu can be used to select a time range for each day of the week
in which, in order to save operating costs, the domestic hot water storage
tank is charged to a higher temperature, e.g. during the low-rate periods
of the power utility.
Setting range: One time range for each day of the week
Default setting: Mon-Sun off
Note: See 10. for the associated temperature settings
The heating circuit setting for the low-rate time period should be
selected appropriately according to the speci
fi
c patterns of use and
the low-rate periods of the relevant power utility.
Caution
The domestic hot water setting for the low-rate time period should
be selected appropriately according to the speci
fi
c patterns of use
and the low-rate periods of the relevant power utility.
Caution