19
Times
Menu 3
8
8
8. Times
Menu “3. Times” is used to set the
time, date, operating times for the
heating circuit and hot water.
8.2 Heating circuit, day
Menu 3.2
This menu is used to select the daytime mode times for the heating circuit;
two time periods can be speci
fi
ed for each weekday and copied over to
the following days.
Setting range: Two time ranges for each day of the week
Default setting: Mon-Sun 06:00-22:00
Note: See 10. for the associated temperature settings
8.1 Time & date
Menu 3.1
This menu is used to set the current time and date.
For proper functioning of the controller and statistics for the system
data it is essential for the time to be set accurately on the controller.
Please note that the clock continues to run for about 24 hours if the
mains voltage is interrupted, and after that has to be reset.
Caution
Caution
Times that are not speci
fi
ed are automatically considered to be
nighttime mode. The set times are only taken into account in the
heating circuit operating mode “Automatic”
8.3 Heating circuit, comf.
Menu 3.3
This menu can be used to select a time range for each day of the week in
which the heating circuit is supplied with an increased comfort temperature,
e.g. for quick heating in the morning.
Setting range: One time range for each day of the week
Default setting: Mon-Sun off
Note: See 10. for the associated temperature settings
Caution
The menu is closed by pressing
“esc” or selecting “Exit display
mode”.
The associated temperature
reference values are speci-
fi
ed in menu 5 “Settings”!