5.4.4.7. Example: Watts per square meter As Analog Sensor
network input config SCPTnvType nciNetworkType =
SNVT_Wm2_p
This input configuration property sets the change of value in W/m² that must result
before the Object will automatically update the following network variables:
•
nv1 – nvoValue_x
Valid Range of Analog Sensor Output
0 … 3276,70 W/m² (Resolution 0.05W/m²)
Default Value of Analog Sensor Output
0 W/m²
5.4.5. Analog Sensor Gain
network input config SNVT_multidiv nciGain;
This input configuration property defines a linear sensor in combination with NV
nciGain_[x] in range of the following network variables:
•
nv1 – nvoValue_x
Multiplier defines the measurement range between minimum, maximum and used
resolution.
Divisor defines the resolution of the used A/D converter, around 2122 for 10 V
Structure Definition
typedef struct {
unsigned long multiplier;
unsigned long divisor;
} SNVT_muldiv;
Valid Range
Multiplier = 0 … 65535 (Resolution 1)
Divisor = 1 … 65535 (Resolution 1)
Default Value
Multiplier = 1