Date: 27.09.17
Functional Profile LON RTS Module WM
animeo LON RTS Module 433/447 MHz . Ref. 51318943A
34/44
5.4.4.1. Example: Send On Power Delta
network input config SNVT_power nciSndDelta;
This input configuration property sets the change of value in Watt that must result
before the Object will automatically update the following network variables:
•
nv1 – nvoValue_x
Valid Range
0,0 … 6553,5W (Resolution 0.1W)
Default Value
10 W (Watt)
5.4.4.2. Example: Send On Percent (CO2) Delta
network input config SNVT_lev_percent nciSndDelta;
This input configuration property sets the change of value in percent that must result
before the Object will automatically update the following network variables:
•
nv1 – nvoValue_x
Valid Range
-163.840 … 163.835 ppm (Resolution 0.005ppm)
Default Value
500 ppm (parts-per-million)
5.4.4.3. Example: Send On Temperatur Delta
network input config SNVT_temp_p nciSndDelta;
This input configuration property sets the change of value in °C that must result before
the Object will automatically update the following network variables:
•
nv1 – nvoValue_x
Valid Range
-273.17 … 327.67°C (Resolution 0.01°C)