Date: 27.09.17
Functional Profile LON RTS Module WM
animeo LON RTS Module 433/447 MHz . Ref. 51318943A
32/44
Valid Range of Analog Sensor Output
0 = OC_OCCUPIED
1 = OC_UNOCCUPIED
Default Value of Analog Sensor Output
-1 = OC_NUL
5.4.1.5. Example: Watts per square meter As Analog Sensor
network input config SCPTnvType nciNetworkType =
SNVT_Wm2_p
This input configuration property sets the global radiation value in W/m² at the
following network variables:
•
nv1 – nvoValue_x
Valid Range of Analog Sensor Output
0 … 3276,70 W/m² (Resolution 0.05W/m²)
Default Value of Analog Sensor Output
0 W/m²
5.4.2. Max Send Time (Heartbeat)
network input config SNVT_time_sec nciMaxSendTime;
This input configuration property sets the maximum period of time that can expire
before the Object will automatically (cyclically) update one of the following network
variables:
•
nv1 – nvoValue_x
Valid Range
0 … 6553.5 seconds (only complete seconds will be processed)
Default Value
0.0 seconds (no automatic update).