Date: 27.09.17
Functional Profile LON RTS Module WM
animeo LON RTS Module 433/447 MHz . Ref. 51318943A
30/44
Valid Range
nvoValue of following type categories are supported:
•
NVT_CAT_UNSIGNED_SHORT e. g. SNVT_lev_cont
•
NVT_CAT_SIGNED_LONG e. g. SNVT_temp
•
NVT_CAT_UNSIGNED_LONG e. g. SNVT_Wm2_p
•
NVT_CAT_STRUCT: only SNVT_switch
•
NVT_CAT_ENUM: only SNVT_occupancy
Default Value
SNVT_lux,
PID 0:0:0:0:0:0:0:0, Scope 0, Index 79, NVT_CAT_UNSIGNED_LONG, 2 bytes,
A=1, B=0, C=0
SCPT Reference
SCPTnvType (254)
Configuration Considerations
The type can only be changed if the nvoValue_x is not bound to any other NV. If this
is not observed or if an unsupported type is set the device goes offline and restores the
previous setting.
5.4.1.1. Example: CO2 As Analog Sensor
network input config SCPTnvType nciNetworkType =
SNVT_lev_percent;
This input configuration property sets the carbon dioxide (CO²) value in parts-per-
million (ppm) at the following network variables:
•
nv1 – nvoValue_x
Valid Range of Analog Sensor Output
-163.840 … 163.835 ppm (Resolution 0.001ppm)
Default Value of Analog Sensor Output
0 ppm (parts-per-million)