Date: 27.09.17
Functional Profile LON RTS Module WM
animeo LON RTS Module 433/447 MHz . Ref. 51318943A
13/44
When Transmitted
The output variable is transmitted when either of the following conditions occurs:
During file transfer
When polled
Default Service Type
The default service type is
unspecified
. Network tools may wish to poll this network
variable for values.
3.3.4. Programming Mode
network input SNVT_switch nviProgMode;
This input network variable activates the programming mode to collect further radio
transmitter devices. Once switched on the device listens for any programming telegram
in the air. As soon as a new radio transmitter message was received the NV changes
back to off and stores the address of the transmitter in the next free memory space.
It is not possible to link one radio transmitter multiple times to one interface device.
Valid Range
The valid range is the range of SNVT_switch.
Default Value
The default value is “0.0 0” (value=0; state=0).
Configuration Considerations
Don’t forget to save the received address (es)! After a timeout of one hour the device
aborts the programming. See nciTransmitterAddr in RadioCtrl Functional Block(s).