Date: 27.09.17
Functional Profile LON RTS Module WM
animeo LON RTS Module 433/447 MHz . Ref. 51318943A
24/44
4.4.7. Step Angle
network input config UCPTstepAngle nciStepAngle
Angle which is used in setting to tilt blinds up or down if Long Operation time was not
exceeded.
Valid Range
The valid range is 0 to 180,0 degrees.
Default Value
The default value is 0,0 degrees.
Configuration Requirements/Restrictions
The physical capabilities of the blinds and the internal solution of tilt range determine
the smallest possible tilt step angle.
SNVT Reference
SNVT_angle_deg #104
4.4.8. Scroll Step
network input config UCPTscrollStep nciScrollStep
Percentage of value change for tilting and dimming if a scroll message has been
received. For tilting the percentage concerns the range of 180°.
Valid Range
The valid range is 0,0 to 100,0 percent.
Default Value
The default value is 10,0 percent.
Configuration Requirements/Restrictions
Depending on the function entered in nciSettingUp and nciSettingDown scrolling
performs an absolute tilting (function = SET_STATE) or a relative one (any other
function).
The physical capabilities of the blinds and the internal solution of tilt range determine
the smallest possible tilt step angle.