background image

+ - A B

ODT VENT DEH

Sensor Dampers

Remote

FLOA

T

Switch

DH

DH

Gh
Rf
Cf

Gs

Y

W

HV

AC EQUIP

.

G
R
C

W

Y

R
C
G

W

Y

HVAC

EQUIPMENT

THERMOSTAT

EXISTING WIRE
NEW WIRE

OPTIONAL

WIRES

90-1859

(40 VA min)

24 VAC

(PRIMARY ZONE)

NORMALLY CLOSED

+ - A B

ODT VENT

Sensor

Dampers

Remote

DH

DH

Gh
Rf
Cf
Gs

Y

W

HV

AC EQUIP

.

(SECONDARY ZONE)

NORMALLY OPEN

DEH

FLO

AT

Switch

90-1896

NOTE:

 Use 18-22 AWG wire for wiring to HVAC system 

and zone dampers.
Pull off the wiring access cover near the dehumidifier control 

to access the wiring terminals. Snap the wiring access cover 

back into place after completing all wiring.

WIRING TO THE HVAC SYSTEM

When the dehumidifier is ducted to the HVAC system, it 

is recommended that it also be wired to the HVAC system 

as shown in 

Figure 22

. If ducted to the HVAC system 

in return to return configuration, the dehumidifier 

must

 

be wired to the HVAC system to prevent short circuiting 

dehumidified air directly back to the dehumidifier inlet. In 

return to supply ducting configuration, running the HVAC 

fan with the dehumidifier ensures the warm dry air is 

mixed with room air before being discharged to the home. 

NOTE: Make sure the external static pressure does not 

exceed the maximums shown on page 2, and disable 

dehumidification during active air conditioning (see 

DEH W/AC on page 13).

Optional W & Y Wiring

Wire the W and/or Y terminal to the HVAC system when 

using the ventilation feature of the dehumidifier (see 

Ventilation

 on page 16).

Wire the dehumidifier Y terminal to the HVAC system if 

it is desired to disable the dehumidifier compressor from 

operating when the air conditioning is running. See 

DEH 

W/AC

 in 

System Set-up

 on page 13 for additional set up 

steps required to access this feature.

WIRING TO ZONE DAMPERS

Wiring the Dehumidifier to the HVAC System and Zone Dampers

Figure 22. Wiring to HVAC System

Figure 23. Two Zone Wiring On-Board Control

11

Содержание HCWHD3-070

Страница 1: ...er Table of Contents Safety Instructions 1 Specifications 2 Packaging Content 2 Set Up Dehumidifier for Installation 3 Duct Collars 3 Control Location 4 Hard Wire Modification 4 Electrical Specificati...

Страница 2: ...dew point minimum Ventilation 40 F 140 F 0 RH 99 RH non condensing Filter MERV 8 washable Airflow External Static Pressure w c Airflow CFM External Static Pressure w c Airflow CFM External Static Pre...

Страница 3: ...not being used See Figure 2 Make sure there are no bends in the duct coming off the outlet for a minimum of 4 This will ensure that the duct will not interfere with the backflow damper function Figur...

Страница 4: ...ower supply at the 115VAC terminals on the dehumidifier United States Installations Make all electrical connections in accordance with the current edition of the NEC ANSI NFPA 70 and any local codes o...

Страница 5: ...lectrical service at the main fuse or circuit breaker box SIDE PANEL ELECTRICAL SERVICE BOX POWER CORD STRAIN RELIEF 90 1900 Figure 5 Electrical Service Box Location Location Considerations Allow suff...

Страница 6: ...te pump is needed install it in the condensate pan as well Install a condensate overflow safety switch i e float switch in the condensate pan remove the factory installed jumper wire between the Float...

Страница 7: ...illes with 10 Duct Collars Ducting Notes Use insulated duct when the dehumidifier is located in an unconditioned space such as an attic or a garage Use a minimum of 12 of flex duct at the dehumidifier...

Страница 8: ...dehumidification needs of the Primary Zone have been satisfied NOTE Dehumidifier controls will not work with iHarmony Zoning Systems IMPORTANT Normally Closed dampers must be installed in the ducts se...

Страница 9: ...he compressor has a 3 minute minimum on and off time NOTE Both the ComfortSense 7000 7500 Thermostat and the iComfort Thermostats use reverse logic for dehumidification There is 24VAC between the DH a...

Страница 10: ...used If an external control is used in a zoned application it must be located in the Primary Zone refer to TWO ZONE PRIMARY AND SECONDARY zoned installation on page 15 for details NOTE When using an e...

Страница 11: ...wired to the HVAC system to prevent short circuiting dehumidified air directly back to the dehumidifier inlet In return to supply ducting configuration running the HVAC fan with the dehumidifier ensu...

Страница 12: ...o to the ZONE screen selections System Set up and Checkout If dehumidifier installation does not include ventilation or zoning and will not be wired to an external control remote control or the HVAC s...

Страница 13: ...select DISABLED and press MODE to go to the EXTERNAL control screen selections 90 1854 If installing the dehumidifier in a two zone application use the UP or DOWN arrows to select ENABLED and press MO...

Страница 14: ...TEST will show on the display If wired to the HVAC system the HVAC blower will turn on and if there is are damper s wired to the DEH DAMPER terminals of the control the damper s will energize 90 1854...

Страница 15: ...alling for dehumidification The dehumidifier and HVAC blower if on will turn off when the RH measured by the Y6456 drops 3 RH below the setting CRAWL SPACE OR SEALED ATTIC REMOTE CONTROL USING Y6456 1...

Страница 16: ...lation is only allowed during a HVAC heat call Vent Auto C Ventilation prevented when outdoor temperature is below 0 F and above 100 F Vent Auto D Ventilation prevented when outdoor temperature is bel...

Страница 17: ...resh Air Delivery Rate 1 Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet 2 See Table 2 for estima...

Страница 18: ...NSTALLER SETTINGS 90 1854 With the dehumidifier power switch on press the ON OFF button to turn the dehumidifier off 90 1854 Press and hold the MODE button for 3 seconds to access the installer settin...

Страница 19: ...the dehumidifier compressor will turn on to remove moisture Ventilation with an External Control When an external control is installed the dehumidifier will open the ventilation damper only when ther...

Страница 20: ...SAMPLING and ON the humidity measured by the internal sensor while also displaying RH and ON and the frost sensor temperature while also displaying ON Scroll through these values and by using the UP D...

Страница 21: ...LER TEST mode Incorrect damper wiring or bad connection Verify wiring between dampers and 24 VAC transformer If wired for Two Zone operation verify that 24 VAC transformer is 40 VA minimum Check all w...

Страница 22: ...SENSOR LOW TEMP SENSOR HI TEMP JUMPER ORG BLUE 24 VAC CMP_N CMP_L FAN_N FAN_L NTRL_F NTRL_C LINE_F LINE_C C S R ORG RED BRN BRN BLK BLK BRN BLU GRN YEL GRN BLK BLK WHT WHT BLK WHT N L WHT BLU RED YEL...

Страница 23: ...Deh Y6467 Fan 95pt Deh Y6468 No Part Description Part No 12 Wire Harness Power Deh Y6469 13 Sensor Low Temperature Deh Y6470 14 Sensor High Temperature Deh Y6471 15 Leveling Foot Deh Y6472 16 Capacito...

Страница 24: ...1 6 Door Filter Access Deh Y7121 7 Outlet Duct Panel Deh Y6463 8 Backflow Damper 10 Deh Y6464 9 Inlet Duct Panel Deh Y6465 10 Cover Outlet Deh Y6466 No Part Description Part No 11 Fan 130pt Deh with 1...

Отзывы: