background image

Table 5. Troubleshooting Guide 

Symptom

Possible Reason

Troubleshooting Procedure

Dehumidifier does not 

turn on/run.

No power to unit.

•   Check that the dehumidifier is plugged in.
•   Check that the power switch is turned ON.
•   Check that the control is turned ON.
•   Check that the circuit breaker has not tripped.

Dehumidifier blower is 

running but with little 

or no airflow.

Pressure drop across 

dehumidifier is 

higher than 0.4"w.c. 

for HCWHD3-070, 

0.6"w.c. for  

HCWHD3-095, or 

0.7"w.c. for  

HCWHD3-130.

•   Check dehumidifier air filter and wash or replace.
•   Check for blocked duct and clear.
•   Verify that the outlet collar with backflow damper is installed on the outlet side of the 

dehumidifier. 

•   Check if backflow damper is blocked or stuck and remove obstruction.

Dehumidifier blower 

is running but 

compressor is not.

Float switch open.

•   If float switch installed, check connections at control board and empty condensate pan.
•   If no float switch installed check that the jumper is installed at the float switch terminals on the 

control board.

Coil frosting.

•   Lack of or reduced airflow. Check dehumidifier air filter and wash or replace.
•   Check for blocked duct.
•   Inlet air conditions below 60°F. Increase the humidity setting.

Inlet air temperature 

is outside of the 

50°F – 104°F range 

or the dew point 

is below 40°F and 

there is a demand for 

dehumidification.

•   Verify all duct is properly sealed.

When zoned, the 

dehumidifier damper 

does not open in 

INSTALLER TEST 

mode.

Incorrect damper 

wiring or bad 

connection.

•   Verify wiring between dampers and 24 VAC transformer.
•   If wired for Two Zone operation, verify that 24 VAC transformer is 40 VA minimum.
•   Check all wiring connections between dampers and control board.
•   Verify the normally closed dampers are in the Primary Zone duct system and the normally 

open dampers are in the Secondary Zone duct system.

The ventilation 

damper does not open 

when the HVAC fan is 

active.

Cycle time has been 

met.

•   The damper will not open if the Ventilation Time has already been met.

ODT error or outdoor 

air outside of ODT 

range.

•   Check that the ODT is wired correctly to the 

dehumidifier control board and connections are 

secure.

•   Check that the ODT is installed in the outdoor 

air intake according to the set-up specified in the 

Ventilation Section beginning on page 16.

•   Remove the ODT leads from the dehumidifier 

control board and check the resistance. Compare 

the reading with the table shown. 

Outdoor 

Temperature

Resistance

0°F

84,500 Ohms

20°F

46,000 Ohms

40°F

26,000 Ohms

60°F

15,500 Ohms

80°F

9,500 Ohms

100°F

6,000 Ohms

Dehumidifier is not 

draining properly.

Drain line blocked or 

unit not level.

•   Verify that the unit is level.
•   Check the drain line blockages and for a continuous downward slope.

The HVAC fan turns 

on unexpectedly.

Dehumidifier is 

sampling or ventilation 

in progress.

•   The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the 

ventilation time.

Dehumidifier is 

producing hot air.

Normal function.

•   Air is reheated across the condenser coil, resulting in a temperature rise between inlet and 

outlet.

21

Содержание HCWHD3-070

Страница 1: ...er Table of Contents Safety Instructions 1 Specifications 2 Packaging Content 2 Set Up Dehumidifier for Installation 3 Duct Collars 3 Control Location 4 Hard Wire Modification 4 Electrical Specificati...

Страница 2: ...dew point minimum Ventilation 40 F 140 F 0 RH 99 RH non condensing Filter MERV 8 washable Airflow External Static Pressure w c Airflow CFM External Static Pressure w c Airflow CFM External Static Pre...

Страница 3: ...not being used See Figure 2 Make sure there are no bends in the duct coming off the outlet for a minimum of 4 This will ensure that the duct will not interfere with the backflow damper function Figur...

Страница 4: ...ower supply at the 115VAC terminals on the dehumidifier United States Installations Make all electrical connections in accordance with the current edition of the NEC ANSI NFPA 70 and any local codes o...

Страница 5: ...lectrical service at the main fuse or circuit breaker box SIDE PANEL ELECTRICAL SERVICE BOX POWER CORD STRAIN RELIEF 90 1900 Figure 5 Electrical Service Box Location Location Considerations Allow suff...

Страница 6: ...te pump is needed install it in the condensate pan as well Install a condensate overflow safety switch i e float switch in the condensate pan remove the factory installed jumper wire between the Float...

Страница 7: ...illes with 10 Duct Collars Ducting Notes Use insulated duct when the dehumidifier is located in an unconditioned space such as an attic or a garage Use a minimum of 12 of flex duct at the dehumidifier...

Страница 8: ...dehumidification needs of the Primary Zone have been satisfied NOTE Dehumidifier controls will not work with iHarmony Zoning Systems IMPORTANT Normally Closed dampers must be installed in the ducts se...

Страница 9: ...he compressor has a 3 minute minimum on and off time NOTE Both the ComfortSense 7000 7500 Thermostat and the iComfort Thermostats use reverse logic for dehumidification There is 24VAC between the DH a...

Страница 10: ...used If an external control is used in a zoned application it must be located in the Primary Zone refer to TWO ZONE PRIMARY AND SECONDARY zoned installation on page 15 for details NOTE When using an e...

Страница 11: ...wired to the HVAC system to prevent short circuiting dehumidified air directly back to the dehumidifier inlet In return to supply ducting configuration running the HVAC fan with the dehumidifier ensu...

Страница 12: ...o to the ZONE screen selections System Set up and Checkout If dehumidifier installation does not include ventilation or zoning and will not be wired to an external control remote control or the HVAC s...

Страница 13: ...select DISABLED and press MODE to go to the EXTERNAL control screen selections 90 1854 If installing the dehumidifier in a two zone application use the UP or DOWN arrows to select ENABLED and press MO...

Страница 14: ...TEST will show on the display If wired to the HVAC system the HVAC blower will turn on and if there is are damper s wired to the DEH DAMPER terminals of the control the damper s will energize 90 1854...

Страница 15: ...alling for dehumidification The dehumidifier and HVAC blower if on will turn off when the RH measured by the Y6456 drops 3 RH below the setting CRAWL SPACE OR SEALED ATTIC REMOTE CONTROL USING Y6456 1...

Страница 16: ...lation is only allowed during a HVAC heat call Vent Auto C Ventilation prevented when outdoor temperature is below 0 F and above 100 F Vent Auto D Ventilation prevented when outdoor temperature is bel...

Страница 17: ...resh Air Delivery Rate 1 Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet 2 See Table 2 for estima...

Страница 18: ...NSTALLER SETTINGS 90 1854 With the dehumidifier power switch on press the ON OFF button to turn the dehumidifier off 90 1854 Press and hold the MODE button for 3 seconds to access the installer settin...

Страница 19: ...the dehumidifier compressor will turn on to remove moisture Ventilation with an External Control When an external control is installed the dehumidifier will open the ventilation damper only when ther...

Страница 20: ...SAMPLING and ON the humidity measured by the internal sensor while also displaying RH and ON and the frost sensor temperature while also displaying ON Scroll through these values and by using the UP D...

Страница 21: ...LER TEST mode Incorrect damper wiring or bad connection Verify wiring between dampers and 24 VAC transformer If wired for Two Zone operation verify that 24 VAC transformer is 40 VA minimum Check all w...

Страница 22: ...SENSOR LOW TEMP SENSOR HI TEMP JUMPER ORG BLUE 24 VAC CMP_N CMP_L FAN_N FAN_L NTRL_F NTRL_C LINE_F LINE_C C S R ORG RED BRN BRN BLK BLK BRN BLU GRN YEL GRN BLK BLK WHT WHT BLK WHT N L WHT BLU RED YEL...

Страница 23: ...Deh Y6467 Fan 95pt Deh Y6468 No Part Description Part No 12 Wire Harness Power Deh Y6469 13 Sensor Low Temperature Deh Y6470 14 Sensor High Temperature Deh Y6471 15 Leveling Foot Deh Y6472 16 Capacito...

Страница 24: ...1 6 Door Filter Access Deh Y7121 7 Outlet Duct Panel Deh Y6463 8 Backflow Damper 10 Deh Y6464 9 Inlet Duct Panel Deh Y6465 10 Cover Outlet Deh Y6466 No Part Description Part No 11 Fan 130pt Deh with 1...

Отзывы: