Determine Cycle Time

1.  Use the Required CFM and Delivered CFM from the above steps to determine the Cycle Time from 

Table 3

.

2.  The values highlighted in gray cannot be set due to the maximum 60 minute Cycle Time. A second ventilation device 

(i.e., bigger duct or second duct) will be required to meet ventilation needs.

Table 3. Cycle Time Setting (minutes) for Airflow Delivered vs. Airflow Required for 1 Hour Cycle

CFM Delivered

CFM Required

20

30

40

50

60

70

80

90

100

60

20

30

40

50

60

70

80

90

100

80

15

25

30

40

45

55

60

70

75

100

15

20

25

30

35

40

50

55

60

120

10

15

20

25

30

35

40

45

50

140

10

15

15

20

25

30

35

40

45

160

10

10

15

20

25

25

30

35

40

INSTALLER SETTINGS 

90-1854

With the dehumidifier 

power switch on, press the 

ON/OFF button to turn the 

dehumidifier off. 

90-1854

Press and hold the MODE 

button for 3 seconds 

to access the installer 

settings menu. Press 

and release the MODE 

button repeatedly until the 

VENT DISABLED screen 

appears.

90-1854

Press the UP or DOWN 

button to ENABLE 

ventilation, then press the 

MODE button to set Timed 

or Auto ventilation.

90-1854

Press the UP or DOWN 

to toggle between VENT 

TIMED, VENT AUTO-B, 

VENT AUTO-C and VENT 

AUTO-D (refer to page 

16 for a description of 

each). Press the MODE 

button to select the desired 

ventilation method and 

adjust the ventilation time.

90-1854

Press the UP or DOWN 

button to set the desired 

amount of ventilation time 

per hour from  

0 to 60 minutes.

90-1854

To complete, press the 

MODE button repeatedly 

until DONE appears on the 

display.

18

Содержание HCWHD3-070

Страница 1: ...er Table of Contents Safety Instructions 1 Specifications 2 Packaging Content 2 Set Up Dehumidifier for Installation 3 Duct Collars 3 Control Location 4 Hard Wire Modification 4 Electrical Specificati...

Страница 2: ...dew point minimum Ventilation 40 F 140 F 0 RH 99 RH non condensing Filter MERV 8 washable Airflow External Static Pressure w c Airflow CFM External Static Pressure w c Airflow CFM External Static Pre...

Страница 3: ...not being used See Figure 2 Make sure there are no bends in the duct coming off the outlet for a minimum of 4 This will ensure that the duct will not interfere with the backflow damper function Figur...

Страница 4: ...ower supply at the 115VAC terminals on the dehumidifier United States Installations Make all electrical connections in accordance with the current edition of the NEC ANSI NFPA 70 and any local codes o...

Страница 5: ...lectrical service at the main fuse or circuit breaker box SIDE PANEL ELECTRICAL SERVICE BOX POWER CORD STRAIN RELIEF 90 1900 Figure 5 Electrical Service Box Location Location Considerations Allow suff...

Страница 6: ...te pump is needed install it in the condensate pan as well Install a condensate overflow safety switch i e float switch in the condensate pan remove the factory installed jumper wire between the Float...

Страница 7: ...illes with 10 Duct Collars Ducting Notes Use insulated duct when the dehumidifier is located in an unconditioned space such as an attic or a garage Use a minimum of 12 of flex duct at the dehumidifier...

Страница 8: ...dehumidification needs of the Primary Zone have been satisfied NOTE Dehumidifier controls will not work with iHarmony Zoning Systems IMPORTANT Normally Closed dampers must be installed in the ducts se...

Страница 9: ...he compressor has a 3 minute minimum on and off time NOTE Both the ComfortSense 7000 7500 Thermostat and the iComfort Thermostats use reverse logic for dehumidification There is 24VAC between the DH a...

Страница 10: ...used If an external control is used in a zoned application it must be located in the Primary Zone refer to TWO ZONE PRIMARY AND SECONDARY zoned installation on page 15 for details NOTE When using an e...

Страница 11: ...wired to the HVAC system to prevent short circuiting dehumidified air directly back to the dehumidifier inlet In return to supply ducting configuration running the HVAC fan with the dehumidifier ensu...

Страница 12: ...o to the ZONE screen selections System Set up and Checkout If dehumidifier installation does not include ventilation or zoning and will not be wired to an external control remote control or the HVAC s...

Страница 13: ...select DISABLED and press MODE to go to the EXTERNAL control screen selections 90 1854 If installing the dehumidifier in a two zone application use the UP or DOWN arrows to select ENABLED and press MO...

Страница 14: ...TEST will show on the display If wired to the HVAC system the HVAC blower will turn on and if there is are damper s wired to the DEH DAMPER terminals of the control the damper s will energize 90 1854...

Страница 15: ...alling for dehumidification The dehumidifier and HVAC blower if on will turn off when the RH measured by the Y6456 drops 3 RH below the setting CRAWL SPACE OR SEALED ATTIC REMOTE CONTROL USING Y6456 1...

Страница 16: ...lation is only allowed during a HVAC heat call Vent Auto C Ventilation prevented when outdoor temperature is below 0 F and above 100 F Vent Auto D Ventilation prevented when outdoor temperature is bel...

Страница 17: ...resh Air Delivery Rate 1 Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet 2 See Table 2 for estima...

Страница 18: ...NSTALLER SETTINGS 90 1854 With the dehumidifier power switch on press the ON OFF button to turn the dehumidifier off 90 1854 Press and hold the MODE button for 3 seconds to access the installer settin...

Страница 19: ...the dehumidifier compressor will turn on to remove moisture Ventilation with an External Control When an external control is installed the dehumidifier will open the ventilation damper only when ther...

Страница 20: ...SAMPLING and ON the humidity measured by the internal sensor while also displaying RH and ON and the frost sensor temperature while also displaying ON Scroll through these values and by using the UP D...

Страница 21: ...LER TEST mode Incorrect damper wiring or bad connection Verify wiring between dampers and 24 VAC transformer If wired for Two Zone operation verify that 24 VAC transformer is 40 VA minimum Check all w...

Страница 22: ...SENSOR LOW TEMP SENSOR HI TEMP JUMPER ORG BLUE 24 VAC CMP_N CMP_L FAN_N FAN_L NTRL_F NTRL_C LINE_F LINE_C C S R ORG RED BRN BRN BLK BLK BRN BLU GRN YEL GRN BLK BLK WHT WHT BLK WHT N L WHT BLU RED YEL...

Страница 23: ...Deh Y6467 Fan 95pt Deh Y6468 No Part Description Part No 12 Wire Harness Power Deh Y6469 13 Sensor Low Temperature Deh Y6470 14 Sensor High Temperature Deh Y6471 15 Leveling Foot Deh Y6472 16 Capacito...

Страница 24: ...1 6 Door Filter Access Deh Y7121 7 Outlet Duct Panel Deh Y6463 8 Backflow Damper 10 Deh Y6464 9 Inlet Duct Panel Deh Y6465 10 Cover Outlet Deh Y6466 No Part Description Part No 11 Fan 130pt Deh with 1...

Отзывы: