background image

SEQUENCE OF OPERATION

When wired as shown in 

Figure 26

, the ventilation damper 

will open whenever there is an HVAC heating (W), cooling 

(Y) or fan (Gs) call, allowing fresh air to be brought in when 

the HVAC blower is running (see VENTILATION WITH 

AN EXTERNAL CONTROL section below for exceptions). 

The ventilation damper will also open if the dehumidifier is 

operating. “VENTILATING” will show on the dehumidifier 

control when the dehumidifier is actively ventilating. When 

the HVAC call ends, the dehumidifier stops, or after the set 

amount of ventilation time has been met, the ventilation 

damper will be closed.
If the set amount of ventilation time has not been met 

before the end of the one-hour cycle, the dehumidifier will 

open the ventilation damper and turn on the HVAC blower 

to ensure the desired ventilation time is satisfied.
If the dehumidifier has been set up to operate ventilation 

with outdoor temperature restrictions (AUTO-B, AUTO-C or 

AUTO-D – refer to page 16) then ventilation will be limited 

as described.

Dehumidifying the Fresh Air

When the dehumidifier is set up for single zone and there 

is no external control installed, the dehumidifier will turn 

on its blower and measure the RH of the air entering the 

dehumidifier during ventilation when ducted as shown in 

Figure 24

. If the relative humidity of the air entering the 

dehumidifier is higher than the setting, the dehumidifier 

compressor will turn on to remove moisture.

Ventilation with an External Control

When an external control is installed the dehumidifier will 

open the ventilation damper only when there is a cooling 

call (Y) or when the dehumidifier is operating, unless the 

ventilation need has not been met. If the set amount of 

ventilation time has not been met before the end of the 

one-hour cycle, the dehumidifier will open the ventilation 

damper and turn on the HVAC blower to ensure the desired 

ventilation time is satisfied.

Adjusting Ventilation Time After Initial Set Up

90-1854

1.

  Press the UP or DOWN 

button to access the RH 

adjustment screen or to 

turn on the backlight if 

using an External Control.

90-1854

2.

  Press the MODE button 

to toggle to the VENT 

TIME setting.

3.

  Press the UP or DOWN 

button to adjust the 

ventilation time (minutes). 

After adjusted, press 

nothing else; the screen 

will return to home screen 

after three (3) seconds.

Troubleshooting

Technical Support is available Monday through Friday, 

6:30 a.m. to 6:30 p.m. CST, at 1-800-LENNOX (800-453-

6669). Use the guides on the following pages to identify 

and correct system faults. Contact Technical Support before 

replacing the unit or any components and for additional 

troubleshooting.

ERROR CODES

When an error occurs, the Error Code along with SERVICE 

REQUIRED will be displayed on the control screen. See 

Table 4

 for possible Error Codes and 

Table 5

 for the 

Troubleshooting Guide.

90-1854

NOTE: Do not try to service the refrigeration compo-

nents in the dehumidifier. Call Technical Support for 

assistance.

19

Содержание HCWHD3-070

Страница 1: ...er Table of Contents Safety Instructions 1 Specifications 2 Packaging Content 2 Set Up Dehumidifier for Installation 3 Duct Collars 3 Control Location 4 Hard Wire Modification 4 Electrical Specificati...

Страница 2: ...dew point minimum Ventilation 40 F 140 F 0 RH 99 RH non condensing Filter MERV 8 washable Airflow External Static Pressure w c Airflow CFM External Static Pressure w c Airflow CFM External Static Pre...

Страница 3: ...not being used See Figure 2 Make sure there are no bends in the duct coming off the outlet for a minimum of 4 This will ensure that the duct will not interfere with the backflow damper function Figur...

Страница 4: ...ower supply at the 115VAC terminals on the dehumidifier United States Installations Make all electrical connections in accordance with the current edition of the NEC ANSI NFPA 70 and any local codes o...

Страница 5: ...lectrical service at the main fuse or circuit breaker box SIDE PANEL ELECTRICAL SERVICE BOX POWER CORD STRAIN RELIEF 90 1900 Figure 5 Electrical Service Box Location Location Considerations Allow suff...

Страница 6: ...te pump is needed install it in the condensate pan as well Install a condensate overflow safety switch i e float switch in the condensate pan remove the factory installed jumper wire between the Float...

Страница 7: ...illes with 10 Duct Collars Ducting Notes Use insulated duct when the dehumidifier is located in an unconditioned space such as an attic or a garage Use a minimum of 12 of flex duct at the dehumidifier...

Страница 8: ...dehumidification needs of the Primary Zone have been satisfied NOTE Dehumidifier controls will not work with iHarmony Zoning Systems IMPORTANT Normally Closed dampers must be installed in the ducts se...

Страница 9: ...he compressor has a 3 minute minimum on and off time NOTE Both the ComfortSense 7000 7500 Thermostat and the iComfort Thermostats use reverse logic for dehumidification There is 24VAC between the DH a...

Страница 10: ...used If an external control is used in a zoned application it must be located in the Primary Zone refer to TWO ZONE PRIMARY AND SECONDARY zoned installation on page 15 for details NOTE When using an e...

Страница 11: ...wired to the HVAC system to prevent short circuiting dehumidified air directly back to the dehumidifier inlet In return to supply ducting configuration running the HVAC fan with the dehumidifier ensu...

Страница 12: ...o to the ZONE screen selections System Set up and Checkout If dehumidifier installation does not include ventilation or zoning and will not be wired to an external control remote control or the HVAC s...

Страница 13: ...select DISABLED and press MODE to go to the EXTERNAL control screen selections 90 1854 If installing the dehumidifier in a two zone application use the UP or DOWN arrows to select ENABLED and press MO...

Страница 14: ...TEST will show on the display If wired to the HVAC system the HVAC blower will turn on and if there is are damper s wired to the DEH DAMPER terminals of the control the damper s will energize 90 1854...

Страница 15: ...alling for dehumidification The dehumidifier and HVAC blower if on will turn off when the RH measured by the Y6456 drops 3 RH below the setting CRAWL SPACE OR SEALED ATTIC REMOTE CONTROL USING Y6456 1...

Страница 16: ...lation is only allowed during a HVAC heat call Vent Auto C Ventilation prevented when outdoor temperature is below 0 F and above 100 F Vent Auto D Ventilation prevented when outdoor temperature is bel...

Страница 17: ...resh Air Delivery Rate 1 Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet 2 See Table 2 for estima...

Страница 18: ...NSTALLER SETTINGS 90 1854 With the dehumidifier power switch on press the ON OFF button to turn the dehumidifier off 90 1854 Press and hold the MODE button for 3 seconds to access the installer settin...

Страница 19: ...the dehumidifier compressor will turn on to remove moisture Ventilation with an External Control When an external control is installed the dehumidifier will open the ventilation damper only when ther...

Страница 20: ...SAMPLING and ON the humidity measured by the internal sensor while also displaying RH and ON and the frost sensor temperature while also displaying ON Scroll through these values and by using the UP D...

Страница 21: ...LER TEST mode Incorrect damper wiring or bad connection Verify wiring between dampers and 24 VAC transformer If wired for Two Zone operation verify that 24 VAC transformer is 40 VA minimum Check all w...

Страница 22: ...SENSOR LOW TEMP SENSOR HI TEMP JUMPER ORG BLUE 24 VAC CMP_N CMP_L FAN_N FAN_L NTRL_F NTRL_C LINE_F LINE_C C S R ORG RED BRN BRN BLK BLK BRN BLU GRN YEL GRN BLK BLK WHT WHT BLK WHT N L WHT BLU RED YEL...

Страница 23: ...Deh Y6467 Fan 95pt Deh Y6468 No Part Description Part No 12 Wire Harness Power Deh Y6469 13 Sensor Low Temperature Deh Y6470 14 Sensor High Temperature Deh Y6471 15 Leveling Foot Deh Y6472 16 Capacito...

Страница 24: ...1 6 Door Filter Access Deh Y7121 7 Outlet Duct Panel Deh Y6463 8 Backflow Damper 10 Deh Y6464 9 Inlet Duct Panel Deh Y6465 10 Cover Outlet Deh Y6466 No Part Description Part No 11 Fan 130pt Deh with 1...

Отзывы: