41
9. Troubleshooting
LCD display
Possible actions
Resumable
Fault
Isolation Fault
1. Check the impedance between PV (+) & PV (-) and
the inverter is earthed. The impedance must be
greater than 2M
.
2. Check whether the AC-side has contacts with earth.
Ground I Fault
1. The ground current is too high.
2. After cut off the AC side connection, unplug the
inputs from the PV generator and check the
peripheral AC system.
3. After the cause is cleared, re-plug the PV panel and
AC connection, and check PV-Inverter status.
Grid Fault
Fac Over Range
Vac Over Range
1. Wait for a moment, if the grid returns to normal, PV-
Inverter automatically restarts.
2. Make sure grid voltage and frequency meet the
specifications.
Utility Loss
1. Grid is not connected.
2. Check grid connection cables.
3. Check grid usability.
4. If grid is ok, and the problem persists, maybe the fuse
in the inverter is open, please call service.
Over Temperature
1. The internal temperature is higher than specified
normal value.
2. Find a way to reduce the ambient temperature.
3. Or move the inverter to a cooler environment.
PV over Voltage
1. Check the open PV voltage, see if it is greater than or
too close to 590VDC (for OXYGEN 3400 or OXYGEN
4500 or OXYGEN 5000).
2. If PV voltage is less than 590VDC, and the problem
still occurs, please call local service.
Permanent
Fault
Consistent Fault
Disconnect PV (+) or PV (-) from the input, restart the
inverter.
Relay-Check Fail
1. Disconnect ALL PV (+) or PV (-).
2. Wait for a few seconds.
3. After the LCD switches off, reconnect and check
again.
4. If the problems remain please call local service.
DC INJ High
EEPROM R/W Fail
SCI Failure
AC HCT Fault
GFCI Failure