Installation
and
Operation
Manual
PVI
Series
Inverters
DOCR
‐
070365
‐
E
Page
38
of
57
The
LEDs
on
the
left
indicate
the
operational
status
of
the
inverter.
LED
Light
Status
Indication
Troubleshooting
Power
Light
on
DC
voltage
available
at
the
inverter
No
need,
Standard
Operation
Light
off
Low
DC
or
possible
power
supply
problem
1.
Check
DC
input
polarity
is
correct.
2.
Verify
DC
voltage
above
180VDC.
3.
Verify
DC
disconnect
switch
is
on.
RUN
Light
on
Inverter
is
producing
power
No
need,
Standard
Operation
Flash
Derating
(light
on
0.5s,
light
off
1.5s)
Verify
Inverters
ambient
temperature
isn’t
above
45°C.
NOTE:
If
the
input
power
is
above
the
rated
output
power
the
inverter
will
derate.
Light
off
Inverter
is
not
producing
power
1.
Verify
that
there
is
no
Snow
on
the
array.
2.
Check
if
Error
light
is
on
or
flashing;
if
so
skip
to
Section
10.
GRID
Light
on
AC
voltage
is
available
at
the
inverter
No
need,
Standard
Operation
Flash
AC
voltage
out
of
setting
range
(light
on
0.5s,
light
off
1.5s)
Check
AC
voltage
and
verify
it
is
within
range
IEEE
1547
specified
range.
Light
off
No
AC
voltage
at
the
inverter
Verify
that
AC
is
available
at
the
inverter.
FAULT
Light
on
Indicates
a
possible
fault
Note
the
LCD
message
and
refer
to
the
Fault
part
of
Section
10.
Slow
flash
Indicates
an
Alarm
(light
on
0.5s,
light
off
2s)
Note
the
LCD
message
and
refer
to
the
Alarm
part
of
Section
10.
Fast
flash
Indicates
protective
action
being
triggered
(light
on
0.5s,
light
off
0.5s)
Note
the
LCD
message
and
refer
to
the
Protection
part
of
Section
10.
Light
off
No
fault
No
need,
Standard
Operation
Table
9.2
–
LED
Indicators
Meaning