PVI
23TL
&
PVI
28TL
Installation
and
Operation
Manual
PVI
Series
Inverters
DOCR
‐
070365
‐
E
Page
16
of
57
3.3.1
Wall
Mounting
The
minimum
distances
that
should
be
met
for
wall
mounting
are
shown
in
Figure
3.2
below.
For
adequate
cooling,
there
should
be
a
minimum
of
≥
20
inches
of
space
available
between
two
adjacently
mounted
inverters.
A
minimum
of
12
inches
from
the
left
side
and
12
inches
from
the
top
are
needed
for
adequate
access
and
cooling.
A
distance
of
24
inches
from
the
bottom
is
recommended
for
the
inverter’s
LCD
to
be
at
eye
level.
If
needed,
this
distance
can
be
lowered
to
10
inches.
Figure
3.2
–
Wall
Mounting
Clearance
Requirements
12.0in
(305mm)
12.0in
(305mm)
20.0in
(508mm)
24.0in
(610mm)