23
Rev. 2
LIST OF POSSIBLE EVENTS
Events
specification
Protection type
Information
on binary
output
available
Description
Oil Pressure
WRN
YES
Measured value is lower than
setpoint.
Oil Pressure
SD .
YES
Measured value is lower than setpoint.
Coolant temp.
WRN
YES
Measured value is greater than
setpoint.
Coolant temp.
SD .
YES
Measured value is greater than setpoint.
Oil temp.
(Optional
equipment)
WRN
YES
Measured value is greater than setpoint.
Oil temp.
(Optional
equipment)
SD .
YES
Measured value is greater than setpoint.
Wrn Batt Volt
WRN
YES
Battery voltage is out of limits given by
Batt
Undervolt/Batt OverVolt
setpoints.
Sd BatteryFlat
SD .
YES
If the controller switches off during starting
sequence due to bad battery condition it doesn’t try
to start again and activates this protection.
Sd Start Fail
SD .
YES
Genset start failed.
Sd Gen Lx >,<V
SD .
YES
The generator voltage is out of limits given by
Gen
<V Sd
and
Gen >V Sd
setpoints.
Sd Gen V Unbal
SD .
YES
The generator voltage is unbalanced more than the
value of
Volt Unbal Sd
setpoint.
Sd Gen >Freq
SD .
YES
The generator frequency is out of limits given by
Gen >Freq Sd
and
Gen <Freq Sd
setpoints.
Wrn Amps Unbal
SD .
NO
The generator current is unbalanced.
Sd Overload
SD .
YES
The load is greater than the value given by
Overload
setpoint.
Sd Overspeed
SD .
YES
The protection comes active if the speed is greater
than
Overspeed
setpoint.
Sd Underspeed
SD .
YES
During starting of the engine when the RPM reach
the value of
Starting RPM
setpoint the starter is
switched off and the speed of the engine can drop
under
Starting RPM
again. Then the Underspeed
protection becomes active. Protection evaluation
starts 5 seconds after reaching
StartingRPM
.
EmergencyStop
SD .
NO
The engine stops immediately when the Emergency
Stop button is pressed and it is not possible to start
the engine again until resetting the Emergency Stop
button.
Sd Stop Fail
SD .
YES
Genset stop failed.
WrnMaintenance
WRN
NO
The period for servicing is set by the
WrnMaintenance
setpoint. The protection comes
active if the running hours of the engine reach this
value.
ChargeAlt Fail
WRN
YES
Failure of alternator for charging the battery.
Sd Override
WRN
NO
The protection is active if the output
Sd Override
is
closed.
Low BackupBatt
WRN
NO
RTC backup battery is flat
Содержание 10 GSC
Страница 2: ...1 Rev 3...
Страница 57: ...U_ 3002_EN Rev 2...
Страница 58: ...1 Rev 2...
Страница 71: ...14 4 1 5 History log...
Страница 99: ...42...
Страница 100: ...43 Rev 2 U_ 3002_EN Rev 2...
Страница 101: ...7 2 Genset Dimensions...
Страница 104: ......
Страница 105: ...7 3 Alternator s Connections...
Страница 106: ......
Страница 107: ......
Страница 108: ...7 4 Regulator s Connections...
Страница 109: ......
Страница 110: ......
Страница 111: ...7 5 Electrical Wiring Drawings...
Страница 116: ...7 6 Tightening Torques...
Страница 118: ...7 7 Instructions for decommissioning scrapping and disposal...